![Daikin FXDQ-SPV1 Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/daikin/fxdq-spv1/fxdq-spv1_engineering-data_3673404033.webp)
FXDQ-SPV1 EDTFVN391825
31
3P347455-11H
6
(2) When the pipe work is completed, please confirm
whether any air is leaked out.
Heat insulation of the pipe on the liquid side
Heat insulation piece for
the pipe (Main unit side)
Heat insulation piece (3) for the
connector (Accessory)
Flare nut connection section
Close firmly to the unit body
The connecting seam
facing upward
Main unit
Banding tie (9)
(Accessory)
Heat insulation piece for
the pipe (supplied on site)
Pipe on the liquid side
Pipe on the air supply side
Heat insulation of the pipe on the air supply side
Heat insulation
piece for the pipe
(main unit side)
Heat insulation piece (4) for the connector
(Accessory)
Flare nut
connection section
The connecting
seam facing upward
Middle seal (6)
(Accessory)
Close firmly to
the unit body
Main unit
Banding tie (9)
(Accessory)
Heat insulation piece for
the pipe (supplied on site)
Wrap on the
flare nut connector.
Fig. 8
Table 2
Pipe dimension
Angle to be further tightened
Recommended length
of the tool arm
60 to 90 degrees
60 to 90 degrees
30 to 60 degrees
30 to 60 degrees
About 150 mm
About 200 mm
About 250 mm
About 300 mm
Ø 6.4 (1/4”)
Ø 9.5 (3/8”)
Ø 12.7 (1/2”)
Ø 15.9 (5/8”)
(3) When it is checked that no air is leaked out, please
refer to Fig. 8 to properly insulate the pipe
connections with heat insulation material.
·
When carrying out heat insulation work, please use
the supplied heat insulation piece (3) (4) for the pipe
of the liquid side and the air supply side. In addition,
the connecting seams of the heat insulation piece (3)
and (4) for the connector shall face upward. (Please
use banding tie (9) to clamp both ends.)
·
Please use the middle seal (6) to wrap the surface of
the heat insulation piece (4) for the connector on the
pipe of the air supply side. (The flare nut section)
The pipe supplied on site must be heat insulated to the
connecting section of the pipe. In case that the pipe is
exposed, condensate can occur, and injury from burning
can also happen if touched.
CAUTION
·
Before welding the refrigerant pipe, please firstly carry
out nitrogen exchange, or when welding (Caution 2),
fill in nitrogen (Caution 1) in the refrigerant pipe, and
finally use the flare to connect to the indoor unit.
(Refer to Fig. 9)
CAUTION
1. In case that nitrogen is filled into the pipe when welding,
a relief valve shall be used to control the pressure to
0.02 MPa (0.2 kgf/cm
2
) (as if breeze flows along your
cheek).
2. When welding the connection section of the refrigerant
pipe, never use any welding flux. Please use phosphorus
and bronze brazing material (BCuP-2: JIS Z 3264/
BCu93P-710/795: ISO 3677) which does not need
welding flux. (In case that any welding flux containing
chlorine is used, the pipe can be corroded; and in case
that any welding flux containing fluorin is used, the ester
oil or ether oil can be deteriorated, and the refrigerant pipe
system can be further influenced.)
Welding position
Relief valve
Wrapping
Nitrogen
Nitrogen
Refrigerant pipe
Manual
valve
Fig. 9
7. DRAIN PIPING WORK
CAUTION
·
The connecting interface of the water drainage pipe
varies depending on different types, so please confirm
the name of the type, and use the installation method
suitable for the type.
(1) Install the water drainage pipe.
Case for Model FXDQ ~ SPV1
Connecting interface of
the water drainage pipe
Refrigerant pipe
Water drainage port for maintenance
(With a rubber plug)
·
When installing the water drainage pipe, ensure that
the water drainage is smooth.
·
The diameter of the water drainage pipe shall be larger
than or equal to that of the connection pipe (polyethylene
pipe; pipe dimensions: 20 mm; outer diameter: 26 mm).
(Not including the riser pipe)
Содержание FXDQ-SPV1
Страница 1: ...FXDQ SPV1 EDTFVN391825 201803 Engineering Data 50 Hz...
Страница 2: ......
Страница 8: ...FXDQ SPV1 EDTFVN391825 6 3 Dimensions FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 3D071829D Unit mm...
Страница 9: ...FXDQ SPV1 EDTFVN391825 7 FXDQ40SPV1 FXDQ50SPV1 3D071831D Unit mm...
Страница 10: ...FXDQ SPV1 EDTFVN391825 8 FXDQ63SPV1 3D071830D Unit mm...
Страница 17: ...FXDQ SPV1 EDTFVN391825 15 9 Fan Performances FXDQ20SPV1 3D072697C...
Страница 18: ...FXDQ SPV1 EDTFVN391825 16 FXDQ25SPV1 3D072698C...
Страница 19: ...FXDQ SPV1 EDTFVN391825 17 FXDQ32SPV1 3D090527...
Страница 20: ...FXDQ SPV1 EDTFVN391825 18 FXDQ40SPV1 FXDQ50SPV1 3D072702C...
Страница 21: ...FXDQ SPV1 EDTFVN391825 19 FXDQ63SPV1 3D090542...
Страница 22: ...FXDQ SPV1 EDTFVN391825 20 10 Sound Levels FXDQ20SPV1 FXDQ25SPV1 4D090507A 4D090508A...
Страница 23: ...FXDQ SPV1 EDTFVN391825 21 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D090509A 4D090510A...
Страница 24: ...FXDQ SPV1 EDTFVN391825 22 FXDQ63SPV1 4D090511A...
Страница 26: ...FXDQ SPV1 EDTFVN391825 24 FXDQ63SPV1 4D072720H Unit mm...
Страница 41: ......
Страница 42: ......
Страница 43: ......