FXDQ-SPV1 EDTFVN391825

33

3P347455-11H

5. Please install the repair cover.

6. Please carry out the following operations for the 

    remote control so as to check the water drainage 

    situations.

   · 

Press the observation / test run button “      ” on 

       the remote control. The air conditioner will enter 

       into the test run mode. Press the run mode select 

       button “      ”, and select the air supply “      ”.

   · 

Press the ON/OFF button “      ”. (The fan and 

       water drainage pump of the indoor unit start to run.)

8

TEST

Case for Model FXDQ ~ SPV1

CAUTION

· 

The electrical wiring work shall be carried out by 

   qualified professional electricians.

· 

When the professional electrician is not on site, 

   please follow Step 3 ~ 7 after the system test run is 

   completed to carry out drainage to confirm that it works.
1. Remove the electrical box cover, and then connect 

    the remote control cable and the power cable 

    (Power supply: Single phase, 50 Hz, 220-240 V) 

    to their corresponding terminal block. Also connect 

    the grounding cable. (Refer to the below figure)

CAUTION

To prevent the wiring connection from being pulled 

by extra tension, please follow the methods as 

shown in Fig. 14 to fix firmly with banding tie (9) 

and (10).

2. Before switching on the power supply, please 

    confirm whether the electrical box cover has been 

    completely covered.

3. Please remove the repair cover.

4. Slowly fill about 1000 cc water into the water 

    drainage pan from the repair opening, so as to 

    check the water drainage situations.

CAUTION

Please never apply any external force to the 

floating valve switch.

(Otherwise error can occur.)

CAUTION

Please note that the fan is also running at this time.

Please never touch the water drainage pump to 

prevent any electrical shock.

TRANSMISSION

WIRING

REMOTE
CONTROL

T1

F1

FORCED

OFF

P2

F2

P1

T2

TRANSMISSION

WIRING

REMOTE
CONTROL

T1

F1

FORCED

OFF

P2

F2

P1

T2

L   N

L

N

Water 

drainage port

Repair opening

Manual pump

Repair cover

Refrigerant

pipe

Water drainage 

port for repair

Water barrel

PCB assy for the indoor unit

Power supply, 

single phase

1~ 220-240 V, 

50 Hz Wiring 

method for the 

power supply 

terminal

Wiring method for the 

remote control terminal

Terminal block

Terminal block

7. Please always use the remote control to switch off 

    to stop water drainage and confirm that it works.

8. INSTALLING THE DUCT

Please connect the air pipe supplied on site.

Air inlet side

· 

Please install the flange on the air supply side 

   (supplied on site).

· 

Please use the supplied bolt (7) to connect the flange 

   and the main body of the air conditioner.

   (Point 12, 14 or 16)

· 

Use sealing materials such as aluminum adhesive tape to 

   seal the connection section between the flange and the 

   air pipe on the air inlet side, so as to prevent air leakage.

CAUTION

· 

Always install the air filter element in the air channel in 

   the air inlet side. (Always select one air filter with the 

   dust collecting efficiency of over 50% (by weight).)

Flange

(Supplied on site)

Main body 

of the 

air conditioner

Flange Heat insulation material

(Supplied on site)

Bolt for connection (7)

(Accessory)

Aluminum adhesive tape

(Supplied on site)

Aluminum adhesive tape

(Supplied on site)

Air supply side

Air outlet side

Air outlet side

· 

Connect the air pipe to the inside of the flange in the 

   air supply side.

· 

Use sealing materials such as aluminum adhesive 

   tape to seal the connection section between the flange 

   and the air pipe on the air outlet side, so as to prevent 

   air leakage.

CAUTION

· 

Always use heat insulation material to prevent condensate 

   on the air pipe. (Material: Glass wool or foamed 

   polyethylene, thickness: 25 mm).

· 

In case that the metal air pipe passes any metal wire, 

   metal wire net or metal plate of any wood structure, ensure 

   that the air pipe and the wall are (electrically) insulated.

· 

Please instruct the operating methods and cleaning 

   methods of the parts supplied on site to the user (air filter, 

   grille (suction inlet and blow outlet), etc.).

9. ELECTRIC WIRING WORK

9-1 General

· 

Before carrying out any electrical work, always switch 

   off the power supply.

· 

Any part and material locally purchased as well as any 

   electrical work shall comply with the local regulations.

· 

Always use copper cables.

· 

When carrying out electrical wiring work, please also 

   refer to the “Wiring Diagram” attached to the electrical 

   box cover.

· 

For details on the wiring of the remote control, please 

   refer to the “Installation instruction manual for remote 

   control” supplied with the remote control.

· 

Any wiring work shall be carried out by qualified 

   professional electricians.

· 

The system consists of many indoor units. Please name 

   the individual indoor units as Unit A, Unit B, …, and 

   confirm whether the cables connecting from the terminal 

   board to the outdoor unit and the BS device match 

   accordingly. In case that any connection of the cables 

   or pipes between the outdoor unit and the indoor unit 

   is incorrect, the air conditioning system will not work 

   normally. To prevent any error, please refer to 

   [Wiring Examples] for wiring.

· 

Wire circuit breaker or electricity leakage circuit breaker 

   must be installed in the power supply point.

· 

The grounding resistance must be below 4 

.

(2) When the pipe work is completed, please check 

      whether the water drainage is smooth.

Содержание FXDQ-SPV1

Страница 1: ...FXDQ SPV1 EDTFVN391825 201803 Engineering Data 50 Hz...

Страница 2: ......

Страница 3: ...ams 10 6 Electric Characteristics 11 7 Safety Devices Setting 12 8 Capacity Tables 13 8 1 Cooling Capacity for Te Auto 13 8 2 Cooling Capacity for Te 6 C 13 8 3 Cooling Capacity for Te 9 C 14 8 4 Heat...

Страница 4: ...5 2 1 Lineup Capacity range 2 2 kW 2 8 kW 3 6 kW 4 5 kW 5 6 kW 7 1 kW 0 8 HP 1 HP 1 25 HP 1 6 HP 2 HP 2 5 HP Capacity index 20 25 31 25 40 50 62 5 FXDQ 20SPV1 25SPV1 32SPV1 40SPV1 50SPV1 63SPV1 V1 1 p...

Страница 5: ...tion manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Wa...

Страница 6: ...manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Washers...

Страница 7: ...on manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Wash...

Страница 8: ...FXDQ SPV1 EDTFVN391825 6 3 Dimensions FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 3D071829D Unit mm...

Страница 9: ...FXDQ SPV1 EDTFVN391825 7 FXDQ40SPV1 FXDQ50SPV1 3D071831D Unit mm...

Страница 10: ...FXDQ SPV1 EDTFVN391825 8 FXDQ63SPV1 3D071830D Unit mm...

Страница 11: ...iagrams FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Refrigerant pipe connection port diameters Unit mm Model Gas Liquid FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 12...

Страница 12: ...FXDQ SPV1 EDTFVN391825 10 5 Wiring Diagrams FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 3D099151...

Страница 13: ...FXDQ SPV1 EDTFVN391825 11 6 Electric Characteristics FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 4D090515...

Страница 14: ...50 V 5 A Fan motor thermal fuse C Fan motor thermal protector C OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 Model FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Printed circuit board fuse A1P 250 V 5 A...

Страница 15: ...gth Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 2 Cooling Capacity for Te 6 C Model Capacity indication Indoor air temp 14 C...

Страница 16: ...These capacity tables are for use when selecting a VRV indoor unit The actual capacity of the VRV system depends on factors such as the selected model of outdoor units outdoor air temperature and pip...

Страница 17: ...FXDQ SPV1 EDTFVN391825 15 9 Fan Performances FXDQ20SPV1 3D072697C...

Страница 18: ...FXDQ SPV1 EDTFVN391825 16 FXDQ25SPV1 3D072698C...

Страница 19: ...FXDQ SPV1 EDTFVN391825 17 FXDQ32SPV1 3D090527...

Страница 20: ...FXDQ SPV1 EDTFVN391825 18 FXDQ40SPV1 FXDQ50SPV1 3D072702C...

Страница 21: ...FXDQ SPV1 EDTFVN391825 19 FXDQ63SPV1 3D090542...

Страница 22: ...FXDQ SPV1 EDTFVN391825 20 10 Sound Levels FXDQ20SPV1 FXDQ25SPV1 4D090507A 4D090508A...

Страница 23: ...FXDQ SPV1 EDTFVN391825 21 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D090509A 4D090510A...

Страница 24: ...FXDQ SPV1 EDTFVN391825 22 FXDQ63SPV1 4D090511A...

Страница 25: ...FXDQ SPV1 EDTFVN391825 23 11 Centre of Gravity FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D072718G Unit mm 4D072719G Unit mm...

Страница 26: ...FXDQ SPV1 EDTFVN391825 24 FXDQ63SPV1 4D072720H Unit mm...

Страница 27: ...s Item Model FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Remote controller Wireless Cooling Only BRC4C66 Heat Pump BRC4C65 Wired BRC1C62 Navigation remote controller Wired remote...

Страница 28: ...ctrical shock or fire Use cables with the specified specifications and all the cables shall be reliably connected and the wiring terminals and the cables are not tensioned by any external force Poor w...

Страница 29: ...ting methods of the various functions as well as the temperature adjustment methods of the air conditioner to the user and ask the user to read the operation manual and carry out operations at the sam...

Страница 30: ...y drained off The strength of the ceiling can withstand the weight of the indoor unit The ceiling is not obviously tilted There is no hazard of possible leakage of combustible gas There is enough spac...

Страница 31: ...an be built in the new ceiling and other items purchased in the market can be used Please refer to Fig 3 Fig 3 Top ceiling Pile anchor screw Long nut or screw thread device Hoisting bolt Note The leng...

Страница 32: ...r air exchange 1 Connect the pipe Refrigerant has been filled in the outdoor unit Align the connecting section of the refrigerant pipe to the center of the flare section and firstly turn 3 4 operation...

Страница 33: ...pipe of the air supply side The flare nut section The pipe supplied on site must be heat insulated to the connecting section of the pipe In case that the pipe is exposed condensate can occur and inju...

Страница 34: ...ng band Water drainage hose 2 Large seal 5 Accessory Metal clip 1 Accessory 4mm Precautions on installing the water drainage riser pipe Case for Model FXDQ SPV1 Please confirm that the height of the w...

Страница 35: ...e air conditioner Point 12 14 or 16 Use sealing materials such as aluminum adhesive tape to seal the connection section between the flange and the air pipe on the air inlet side so as to prevent air l...

Страница 36: ...is within a place easily in contact with people please install an electricity leakage circuit breaker to prevent electrical shock 4 When an electricity leakage circuit breaker is used please use a dev...

Страница 37: ...ng cable to the electrical box When connecting the cables the cables shall be routed orderly and placed even and the electrical box cover shall not be supported up and the electrical box cover shall b...

Страница 38: ...auses as loosened cables When connected to the terminal board please use round wiring terminal with insulated sleeve In case that round wiring terminal with insulated sleeve cannot be used connect the...

Страница 39: ...Electrical Wiring Work 3 Remove the electrical box cover 4 Connect remote control 2 Slave to the terminal board of the remote control cable in the electrical box P1 and P2 No polarity 1 P 2 P 1 F 2 F...

Страница 40: ...Setting the time to display the clean air filter element signal To change the Setting for contamination level of the air filter element tell the following contents to the user The factory setting to d...

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ...rts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation of...

Отзывы: