FXDQ-SPV1 EDTFVN391825
34
3P347455-11H
·
The shielded sections shall be wrapped with materials as
insulated adhesive tape to prevent contact with any other
terminal.
·
The end of the shielded sections shall be closely connected
to the noiseless grounding point marked with .
9
9-2 Specifications of standard wiring parts
·
Never connect the grounding cable to any gas pipe,
running water pipe, lighting rod or telephone line.
·
Gas pipe : Once any gas is leaked out, exposition and
fire can happen.
·
Running water pipe: In case that hard plastic pipe is
used, there will be no grounding function.
·
Telephone grounding line and lighting rod : When
struck by lighting, the grounding potential will become
exceptionally high.
·
To prevent short circuiting of the power cable, insulated
sleeve terminals must be used.
·
Before all the electrical work is completed, no power
supply shall be switched on (wire circuit breaker or
electricity leakage circuit breaker).
Power cable, etc.
Power cable (including grounding cable)
Number
of units
Site fuse
Cable
Dimensions
Comply with the
local regulations.
1
16A
H05VV-U3G
Transmission cable and remote control cable
Cable (Note 5)
• Cases that the connected
outdoor unit is 24 kW or
below
• Cases that the connected
outdoor unit is above 24 kW
Dimensions
(mm
2
)
Shielded cable RVVP
Polyethylene sleeve flexible
cable or power cable
0.75 - 1.25
Notes
1. Over-current circuit breaker can be used to replace
the fuse.
2. The above Type H05VV cable is equal to Type YZW
ordinary rubber sleeve flexible cable specified in
GB5013 or IEC24581.
3. In case that the cable is within a place easily in contact
with people, please install an electricity leakage circuit
breaker to prevent electrical shock.
4. When an electricity leakage circuit breaker is used,
please use a device compatible with grounding over-
current protection and short circuit protection. When
one special grounding protection device is used in the
electricity leakage circuit breaker, always use a wire
circuit breaker at the same time.
5. When the connected outdoor unit is 24 kW or below,
the transmission cable and remote control cable shall
be shielded.
·
The length of the transmission cable and remote control
cable is limited as below.
Length of the transmission cable and remote control cable
Type of outdoor
unit connected
• Horizontal blow type
outdoor unit connected
• Upward blow type
outdoor unit connected
Outdoor unit –
indoor unit
Max. length 300 m
(Total cable length : 600 m)
Max. length 1000 m
(Total cable length : 2000 m)
Indoor unit –
remote control
Max. length 300 m
Max. length 500 m
6. The specifications of the fuse on the circuit board is:
250V, 5A (F1U)
WARNING
: When the fuse is blown out, please
have it replaced by a repair agency,
but never replace it by yourself.
Otherwise accidents as electrical
shock can happen.
7. As the unit is equipped with a frequency converter,
to prevent misoperation of the electricity leakage
circuit breaker itself, please use a product which can
resist against high harmonic wave.
9-3 Electrical features
Air conditioner
Power supply
Fan motor
Model
Hz
Voltage Voltage
range
MCA MFA
KW
FLA
FXDQ20 ~ 32SPV1
FXDQ40 ~ 50SPV1
FXDQ63SPV1
0.7
1.1
1.2
0.062
0.130
0.130
0.5
0.7
0.8
Min.
198 V
Max.
264 V
MCA
: Minimum circuit current (A)
MFA
: Maximum fuse current (A)
KW
: Rated output power of the fan motor (kW)
FLA
: Full load current (A)
50
16
220V
-
240V
Содержание FXDQ-SPV1
Страница 1: ...FXDQ SPV1 EDTFVN391825 201803 Engineering Data 50 Hz...
Страница 2: ......
Страница 8: ...FXDQ SPV1 EDTFVN391825 6 3 Dimensions FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 3D071829D Unit mm...
Страница 9: ...FXDQ SPV1 EDTFVN391825 7 FXDQ40SPV1 FXDQ50SPV1 3D071831D Unit mm...
Страница 10: ...FXDQ SPV1 EDTFVN391825 8 FXDQ63SPV1 3D071830D Unit mm...
Страница 17: ...FXDQ SPV1 EDTFVN391825 15 9 Fan Performances FXDQ20SPV1 3D072697C...
Страница 18: ...FXDQ SPV1 EDTFVN391825 16 FXDQ25SPV1 3D072698C...
Страница 19: ...FXDQ SPV1 EDTFVN391825 17 FXDQ32SPV1 3D090527...
Страница 20: ...FXDQ SPV1 EDTFVN391825 18 FXDQ40SPV1 FXDQ50SPV1 3D072702C...
Страница 21: ...FXDQ SPV1 EDTFVN391825 19 FXDQ63SPV1 3D090542...
Страница 22: ...FXDQ SPV1 EDTFVN391825 20 10 Sound Levels FXDQ20SPV1 FXDQ25SPV1 4D090507A 4D090508A...
Страница 23: ...FXDQ SPV1 EDTFVN391825 21 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D090509A 4D090510A...
Страница 24: ...FXDQ SPV1 EDTFVN391825 22 FXDQ63SPV1 4D090511A...
Страница 26: ...FXDQ SPV1 EDTFVN391825 24 FXDQ63SPV1 4D072720H Unit mm...
Страница 41: ......
Страница 42: ......
Страница 43: ......