FXDQ-SPV1 EDTFVN391825
32
3P347455-11H
7
·
The water drainage pipe shall be short as possible and
tilt downward, and the slope shall be at least 1/100,
so as to prevent the forming of any air trap.
(Refer to Fig. 10)
Over
100 mm
Integrated water drainage pipe
(with a download slope of at least 1/100)
Fig. 10
CAUTION
In case that there is any accumulated water in the
water drainage pipe, blockage can occur.
·
To prevent the pipe from sagging, a hanging cable shall
be used to hang it up every 1 ~ 1.5 m.
·
Please use the water drainage hose (2) and metal
clip (1) in the accessories. The water drainage hose (2)
shall be inserted to the bottom of the water drainage
insertion opening, and the metal clip (1) shall be used for
firm fixing on the marking band in the front of the hose.
Tighten the metal clip (1), until the protruding height of
the bolt head is less than 4 mm.
(Please refer to Fig. 11
and 12)
·
The following two points shall be heat insulated, so as
to prevent any condensate dripping.
·
The indoor water drainage hose
·
The water drainage insertion opening
Please refer to the following figure to use the large
seal (6) in the accessories to carry out heat insulation
for the metal clip (1) and the water drainage hose (2).
(Please refer to Fig. 12)
Fig. 11
Fig. 12
Metal clip (1)
(Accessory)
Marking
band
Water drainage
hose (2)
Large seal (5)
(Accessory)
Metal clip (1)
(Accessory)
4mm
(Precautions on installing the water drainage
riser pipe)
Case for Model FXDQ ~ SPV1
·
Please confirm that the height of the water drainage
riser pipe is within 600 mm.
·
Please keep the water drainage riser pipe vertical,
and ensure that the distance from the air conditioner
is within 300 mm.
(Refer to Fig. 13)
Fig. 13
Ceiling
Within 300 mm
Hanging
cable
Metal clip (1) (accessory)
Water drainage hose (2) (accessory)
Adjustable range
(Within 600 mm)
Water drainage riser pipe
(Supplied on site)
1 ~ 1.5m
Water drainage hose (2)
(accessory)
Horizontal or
tilting up slightly
To prevent any trapped air in the water drainage hose,
please install horizontally or in a slightly tilted up way.
In case that any air is trapped, when the water drainage
pump stops, water drainage can be reversed and
abnormal noise is sent out.
(Notes)
Water drainage pipe connection
·
Never directly connect the water drainage pipe to any
sewage with an ammonia smell. The ammonia in the
sewage can enter into the indoor unit along the water
drainage pipe and corrode the heat exchanger.
·
Never twist or bend the water drainage hose (2), and
never apply too high force on it. (Otherwise water
leakage can occur.)
·
In case that an integrated water drainage pipe is used,
please connect it as shown in Fig. 10.
·
Please select the integrated water drainage pipe with
proper dimensions in accordance with the capacity of
the air conditioner to be connected.
Содержание FXDQ-SPV1
Страница 1: ...FXDQ SPV1 EDTFVN391825 201803 Engineering Data 50 Hz...
Страница 2: ......
Страница 8: ...FXDQ SPV1 EDTFVN391825 6 3 Dimensions FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 3D071829D Unit mm...
Страница 9: ...FXDQ SPV1 EDTFVN391825 7 FXDQ40SPV1 FXDQ50SPV1 3D071831D Unit mm...
Страница 10: ...FXDQ SPV1 EDTFVN391825 8 FXDQ63SPV1 3D071830D Unit mm...
Страница 17: ...FXDQ SPV1 EDTFVN391825 15 9 Fan Performances FXDQ20SPV1 3D072697C...
Страница 18: ...FXDQ SPV1 EDTFVN391825 16 FXDQ25SPV1 3D072698C...
Страница 19: ...FXDQ SPV1 EDTFVN391825 17 FXDQ32SPV1 3D090527...
Страница 20: ...FXDQ SPV1 EDTFVN391825 18 FXDQ40SPV1 FXDQ50SPV1 3D072702C...
Страница 21: ...FXDQ SPV1 EDTFVN391825 19 FXDQ63SPV1 3D090542...
Страница 22: ...FXDQ SPV1 EDTFVN391825 20 10 Sound Levels FXDQ20SPV1 FXDQ25SPV1 4D090507A 4D090508A...
Страница 23: ...FXDQ SPV1 EDTFVN391825 21 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D090509A 4D090510A...
Страница 24: ...FXDQ SPV1 EDTFVN391825 22 FXDQ63SPV1 4D090511A...
Страница 26: ...FXDQ SPV1 EDTFVN391825 24 FXDQ63SPV1 4D072720H Unit mm...
Страница 41: ......
Страница 42: ......
Страница 43: ......