background image

FXDQ-SPV1 EDTFVN391825

37

3P347455-11H

12

1

P

2

P

1

F

2

F

1

T

2

T

REMOTE
CONTROL

TRANSMISSION

WIRING

FORCED

OFF

10-2 Double controls for one unit (One indoor unit 

        controlled by two remote controls)

· 

When two remote controls are used, one must be set 

   to “Master”, and the other must be set to “Slave”. 

   (In case that the remote control is Type BRC1E62, 

   please refer to the installation instruction manual for 

   the remote control.)

Master / Slave switching

(1) Please insert     screwdrivers into the seam 

     between the upper and lower part of the remote 

     control, and use force on both points to carefully 

     pry the upper half open (2 points). 

     The PC board of the remote control is attached in 

     the upper half of the remote control.

Upper half of the remote control

Lower half of the 

remote control

Insert screwdrivers here to slightly turn down 

the upper half of the remote control.

(2) Set the Master / Slave switch on the PC board 

     of any of the two remote controls to “S”.

     (The other remote control is still “M”.)

S

M

S

S

M

(Factory setting)

PC board of the

remote control

In cased that the factory setting 

has not been changed, it is only 

required to change the setting of 

one remote control.

Cable connecting method (Please refer to Section 

“Electrical Wiring Work”.)
(3) Remove the electrical box cover.
(4) Connect remote control 2 (Slave) to the terminal 

      board of the remote control cable in the electrical 

      box (P

1

 and P

2

). (No polarity.) 

1

P

2

P

1

F

2

F

1

T

2

T

FORCED

OFF

REMOTE

CONTROL

TRANSMISSION

WIRING

Terminal board for the 

remote control cable

Remote control 1 

(Master)

Remote control 2 

(Slave)

[Notes]

· 

In case that control by group and double remote 

   controls are used at the same time, it is required to 

   connect a jump cable.

· 

Please connect remote control 2 (Slave) to the indoor 

   unit at the end of the jump cable (P

1

 and P

2

).

Indoor unit 1

Indoor unit 2

Indoor unit with 

the largest number

Jump cable (P

1

 and P

2

)

Remote control 1 

(Master)

Remote control 2

(Slave)

10-3 Remote operated control (Forced off and on / 

        off operation)

· 

Connect the input cable from external to Terminal T1 

   and T2 on the terminal board of the remote control (6P) 

   to carry out remote operated control.

· 

For the details on the operations, please refer to 

   

“11. FIELD SETTING AND TEST RUN”

.

Input A

Cable specifications

Polyethylene sleeve flexible wire or cable (2 cores)

Section area
Length

Max. length 100 m

Specifications of 

external contactor

Minimum applicable load of the contactor 15V DC, 1 mA.

0.75 - 1.25mm

2

10-4 Cases of integrated control

· 

In case that integrated control is used, it is required to 

   set the group number. For details, please refer to the 

   instruction manual for integrated control.

Содержание FXDQ-SPV1

Страница 1: ...FXDQ SPV1 EDTFVN391825 201803 Engineering Data 50 Hz...

Страница 2: ......

Страница 3: ...ams 10 6 Electric Characteristics 11 7 Safety Devices Setting 12 8 Capacity Tables 13 8 1 Cooling Capacity for Te Auto 13 8 2 Cooling Capacity for Te 6 C 13 8 3 Cooling Capacity for Te 9 C 14 8 4 Heat...

Страница 4: ...5 2 1 Lineup Capacity range 2 2 kW 2 8 kW 3 6 kW 4 5 kW 5 6 kW 7 1 kW 0 8 HP 1 HP 1 25 HP 1 6 HP 2 HP 2 5 HP Capacity index 20 25 31 25 40 50 62 5 FXDQ 20SPV1 25SPV1 32SPV1 40SPV1 50SPV1 63SPV1 V1 1 p...

Страница 5: ...tion manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Wa...

Страница 6: ...manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Washers...

Страница 7: ...on manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Wash...

Страница 8: ...FXDQ SPV1 EDTFVN391825 6 3 Dimensions FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 3D071829D Unit mm...

Страница 9: ...FXDQ SPV1 EDTFVN391825 7 FXDQ40SPV1 FXDQ50SPV1 3D071831D Unit mm...

Страница 10: ...FXDQ SPV1 EDTFVN391825 8 FXDQ63SPV1 3D071830D Unit mm...

Страница 11: ...iagrams FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Refrigerant pipe connection port diameters Unit mm Model Gas Liquid FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 12...

Страница 12: ...FXDQ SPV1 EDTFVN391825 10 5 Wiring Diagrams FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 3D099151...

Страница 13: ...FXDQ SPV1 EDTFVN391825 11 6 Electric Characteristics FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 4D090515...

Страница 14: ...50 V 5 A Fan motor thermal fuse C Fan motor thermal protector C OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 Model FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Printed circuit board fuse A1P 250 V 5 A...

Страница 15: ...gth Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 2 Cooling Capacity for Te 6 C Model Capacity indication Indoor air temp 14 C...

Страница 16: ...These capacity tables are for use when selecting a VRV indoor unit The actual capacity of the VRV system depends on factors such as the selected model of outdoor units outdoor air temperature and pip...

Страница 17: ...FXDQ SPV1 EDTFVN391825 15 9 Fan Performances FXDQ20SPV1 3D072697C...

Страница 18: ...FXDQ SPV1 EDTFVN391825 16 FXDQ25SPV1 3D072698C...

Страница 19: ...FXDQ SPV1 EDTFVN391825 17 FXDQ32SPV1 3D090527...

Страница 20: ...FXDQ SPV1 EDTFVN391825 18 FXDQ40SPV1 FXDQ50SPV1 3D072702C...

Страница 21: ...FXDQ SPV1 EDTFVN391825 19 FXDQ63SPV1 3D090542...

Страница 22: ...FXDQ SPV1 EDTFVN391825 20 10 Sound Levels FXDQ20SPV1 FXDQ25SPV1 4D090507A 4D090508A...

Страница 23: ...FXDQ SPV1 EDTFVN391825 21 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D090509A 4D090510A...

Страница 24: ...FXDQ SPV1 EDTFVN391825 22 FXDQ63SPV1 4D090511A...

Страница 25: ...FXDQ SPV1 EDTFVN391825 23 11 Centre of Gravity FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D072718G Unit mm 4D072719G Unit mm...

Страница 26: ...FXDQ SPV1 EDTFVN391825 24 FXDQ63SPV1 4D072720H Unit mm...

Страница 27: ...s Item Model FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Remote controller Wireless Cooling Only BRC4C66 Heat Pump BRC4C65 Wired BRC1C62 Navigation remote controller Wired remote...

Страница 28: ...ctrical shock or fire Use cables with the specified specifications and all the cables shall be reliably connected and the wiring terminals and the cables are not tensioned by any external force Poor w...

Страница 29: ...ting methods of the various functions as well as the temperature adjustment methods of the air conditioner to the user and ask the user to read the operation manual and carry out operations at the sam...

Страница 30: ...y drained off The strength of the ceiling can withstand the weight of the indoor unit The ceiling is not obviously tilted There is no hazard of possible leakage of combustible gas There is enough spac...

Страница 31: ...an be built in the new ceiling and other items purchased in the market can be used Please refer to Fig 3 Fig 3 Top ceiling Pile anchor screw Long nut or screw thread device Hoisting bolt Note The leng...

Страница 32: ...r air exchange 1 Connect the pipe Refrigerant has been filled in the outdoor unit Align the connecting section of the refrigerant pipe to the center of the flare section and firstly turn 3 4 operation...

Страница 33: ...pipe of the air supply side The flare nut section The pipe supplied on site must be heat insulated to the connecting section of the pipe In case that the pipe is exposed condensate can occur and inju...

Страница 34: ...ng band Water drainage hose 2 Large seal 5 Accessory Metal clip 1 Accessory 4mm Precautions on installing the water drainage riser pipe Case for Model FXDQ SPV1 Please confirm that the height of the w...

Страница 35: ...e air conditioner Point 12 14 or 16 Use sealing materials such as aluminum adhesive tape to seal the connection section between the flange and the air pipe on the air inlet side so as to prevent air l...

Страница 36: ...is within a place easily in contact with people please install an electricity leakage circuit breaker to prevent electrical shock 4 When an electricity leakage circuit breaker is used please use a dev...

Страница 37: ...ng cable to the electrical box When connecting the cables the cables shall be routed orderly and placed even and the electrical box cover shall not be supported up and the electrical box cover shall b...

Страница 38: ...auses as loosened cables When connected to the terminal board please use round wiring terminal with insulated sleeve In case that round wiring terminal with insulated sleeve cannot be used connect the...

Страница 39: ...Electrical Wiring Work 3 Remove the electrical box cover 4 Connect remote control 2 Slave to the terminal board of the remote control cable in the electrical box P1 and P2 No polarity 1 P 2 P 1 F 2 F...

Страница 40: ...Setting the time to display the clean air filter element signal To change the Setting for contamination level of the air filter element tell the following contents to the user The factory setting to d...

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ...rts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation of...

Отзывы: