Control Specification
SiENBE04-507A
66
Function and Control
3.5
Input Current Control
Outline
The microcomputer calculates the input current during the compressor is running, and set the
frequency upper limit from such input current.
In case of heat pump model, this control is the upper limit control function of the frequency
which takes priority of the lower limit of four way valve activating compensation.
Detail
Frequency control in each zone
Drooping zone
The maximum limit of the compressor frequency in this control is defined as operation
frequency – 2Hz.
After this, the output frequency is pulled down by 2Hz every second until it reaches the
steady zone.
Keep zone
The present maximum frequency goes on.
Reset zone
Limit of the frequency is cancelled.
Stop zone
After 2.5 s in this zone, the compressor is stopped.
Limitation of current drooping and stop value according to the outdoor air temperature
1. In case the operation mode is cooling
The current droops when outdoor air temperature becomes higher than a certain level
(model by model).
2. In case the operation mode is heating (only for heat pump model)
The current droops when outdoor air temperature becomes higher than a certain level
(model by model).
Compressor Stop
Stop
Zone
Drooping
Zone
Keep
Zone
Reset
Zone
(R4304)
I4
I3
I3 –I
α
I3 (A) Normal
mode
6.0
7.25
7.5
8.25
ECONO
mode 4.25
5.0
5.25
5.75
I3-I
α
(A) Normal
mode
5.25
6.5
6.75
7.5
ECONO
mode 3.5
4.25
4.5
5.0
Cooling
Heating
20/25 class
35 class
20/25 class
35 class
I4 (A)
12
12
Содержание FTKS20DVMW(L)
Страница 10: ...SiENBE04 507A List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 16: ...SiENBE04 507A Specifications 7 Part 2 Specifications 1 Specifications 8 1 1 Cooling Only 8 1 2 Heat Pump 21...
Страница 53: ...Printed Circuit Board Connector Wiring Diagram SiENBE04 507A 44 Printed Circuit Board Connector Wiring Diagram...
Страница 85: ...Control Specification SiENBE04 507A 76 Function and Control...
Страница 159: ...Check SiENBE04 507A 150 Service Diagnosis...
Страница 198: ...SiENBE04 507A Outdoor Unit Removal Procedure 189 When reassembling make sure to fit the hook Step Procedure Points Hook...
Страница 212: ...SiENBE04 507A Others 203 Part 8 Others 1 Others 204 1 1 Test Run from the Remote Controller 204 1 2 Jumper Settings 205...
Страница 215: ...Others SiENBE04 507A 206 Others...
Страница 221: ...Wiring Diagrams SiENBE04 507A 212 Appendix...
Страница 225: ...SiENBE04 507A iv Index...