Troubleshooting
SiENBE04-507A
120
Service Diagnosis
4.8
Outdoor Unit PCB Abnormality
Remote
Controller
Display
E1
Method of
Malfunction
Detection
The system follows the microprocessor program to make sure it runs normally.
The system checks to see if the zero-cross signal comes in properly.
Malfunction
Decision
Conditions
The microprocessor program runs out of control.
The zero-cross signal is not detected.
Supposed
Causes
The microcomputer is out of control due to external factors.
Noise
Momentary voltage drop
Momentary power failure, etc.
Outdoor unit PCB defective
Broken harness between PCBs
Troubleshooting
Turn on the power again.
Replace the outdoor unit
PCB (1).
Ground the system.
Zero-cross signal
abnormality. Replace the
outdoor unit PCB (2).
Replace the harness.
(R4563)
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is LED A flashing?
Grounded?
Is the harness
broken?
Check to see if the system is
grounded.
Caution
NO
YES
NO
YES
NO
YES
Содержание FTKS20DVMW(L)
Страница 10: ...SiENBE04 507A List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 16: ...SiENBE04 507A Specifications 7 Part 2 Specifications 1 Specifications 8 1 1 Cooling Only 8 1 2 Heat Pump 21...
Страница 53: ...Printed Circuit Board Connector Wiring Diagram SiENBE04 507A 44 Printed Circuit Board Connector Wiring Diagram...
Страница 85: ...Control Specification SiENBE04 507A 76 Function and Control...
Страница 159: ...Check SiENBE04 507A 150 Service Diagnosis...
Страница 198: ...SiENBE04 507A Outdoor Unit Removal Procedure 189 When reassembling make sure to fit the hook Step Procedure Points Hook...
Страница 212: ...SiENBE04 507A Others 203 Part 8 Others 1 Others 204 1 1 Test Run from the Remote Controller 204 1 2 Jumper Settings 205...
Страница 215: ...Others SiENBE04 507A 206 Others...
Страница 221: ...Wiring Diagrams SiENBE04 507A 212 Appendix...
Страница 225: ...SiENBE04 507A iv Index...