Troubleshooting
SiENBE04-507A
132
Service Diagnosis
4.18 DC Voltage / Current Sensor Abnormality
Remote
Controller
Display
H8
Method of
Malfunction
Detection
Detecting abnormality of the DC sensor by the running frequency of compressor and by the
input current multiplied DC voltage and current.
Malfunction
Decision
Conditions
The compressor running frequency is below 52 Hz.
(The input current is also below 0.5 A.)
If this error repeats 4 times, the system will be shut down.
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Supposed
Causes
Outdoor unit PCB defective
Troubleshooting
Replace the outdoor unit PCB.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Содержание FTKS20DVMW(L)
Страница 10: ...SiENBE04 507A List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 16: ...SiENBE04 507A Specifications 7 Part 2 Specifications 1 Specifications 8 1 1 Cooling Only 8 1 2 Heat Pump 21...
Страница 53: ...Printed Circuit Board Connector Wiring Diagram SiENBE04 507A 44 Printed Circuit Board Connector Wiring Diagram...
Страница 85: ...Control Specification SiENBE04 507A 76 Function and Control...
Страница 159: ...Check SiENBE04 507A 150 Service Diagnosis...
Страница 198: ...SiENBE04 507A Outdoor Unit Removal Procedure 189 When reassembling make sure to fit the hook Step Procedure Points Hook...
Страница 212: ...SiENBE04 507A Others 203 Part 8 Others 1 Others 204 1 1 Test Run from the Remote Controller 204 1 2 Jumper Settings 205...
Страница 215: ...Others SiENBE04 507A 206 Others...
Страница 221: ...Wiring Diagrams SiENBE04 507A 212 Appendix...
Страница 225: ...SiENBE04 507A iv Index...