SiENBE04-507A
Others
Others
205
1.2
Jumper Settings
1.2.1 When Two Units are Installed in One Room
When two indoor units are installed in one room, the two wireless remote controllers can be set
for different addresses.
How to set the different addresses
Control PCB of the indoor unit
(1) Remove the front grille. (3 screws)
(2) Remove the electrical box (1-screw).
(3) Remove the drip proof plate. (4 tabs)
(4) Cut the address jumper JA on the control PCB.
Wireless remote controller
(1) Slide the front cover and take it off.
(2) Cut the address jumper J4.
1.2.2 Jumper Setting
(R4417)
ADDRESS
JA
ADDRESS
JA
EXIST
1
CUT
2
ADDRESS
J4
EXIST
CUT
1
2
J4
(R4418)
Jumper
(On indoor control PCB)
Function
When connected
(factory set)
When cut
JC
Power failure
recovery function
Auto-restart
Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
JB
Fan speed setting
when compressor is
OFF on thermostat.
Fan speed setting ;
Remote controller
setting
Fan rpm is set to “0”
<Fan stop>
Содержание FTKS20DVMW(L)
Страница 10: ...SiENBE04 507A List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 16: ...SiENBE04 507A Specifications 7 Part 2 Specifications 1 Specifications 8 1 1 Cooling Only 8 1 2 Heat Pump 21...
Страница 53: ...Printed Circuit Board Connector Wiring Diagram SiENBE04 507A 44 Printed Circuit Board Connector Wiring Diagram...
Страница 85: ...Control Specification SiENBE04 507A 76 Function and Control...
Страница 159: ...Check SiENBE04 507A 150 Service Diagnosis...
Страница 198: ...SiENBE04 507A Outdoor Unit Removal Procedure 189 When reassembling make sure to fit the hook Step Procedure Points Hook...
Страница 212: ...SiENBE04 507A Others 203 Part 8 Others 1 Others 204 1 1 Test Run from the Remote Controller 204 1 2 Jumper Settings 205...
Страница 215: ...Others SiENBE04 507A 206 Others...
Страница 221: ...Wiring Diagrams SiENBE04 507A 212 Appendix...
Страница 225: ...SiENBE04 507A iv Index...