Control Specification
SiENBE04-507A
62
Function and Control
3.2
Frequency Control
Outline
Frequency will be determined according to the difference between room and set temperature.
The function is explained as follows.
1. How to determine frequency.
2. Frequency command from an indoor unit. (The difference between a room temperature and
the temperature set by the remote controller.)
3. Frequency command from an indoor unit.
4. Frequency initial setting.
5. PI control.
Detail
How to Determine Frequency
The compressor’s frequency will finally be determined by taking the following steps.
For Heat Pump Model
1. Determine command frequency
Command frequency will be determined in the following order of priority.
1.1 Limiting frequency by drooping function
Input current, discharge pipes, peak cutting, freeze-up protection, dew prevention, fin
thermistor temperature.
1.2 Limiting defrost control time
1.3 Forced cooling
1.4 Indoor frequency command
2. Determine upper limit frequency
Set a minimum value as an upper limit frequency among the frequency upper limits of the
following functions:
Compressor protection, input current, discharge pipes, peak cutting, freeze-up protection,
defrost.
3. Determine lower limit frequency
Set a maximum value as an lower limit frequency among the frequency lower limits of the
following functions:
Four way valve operating compensation, draft prevention, pressure difference upkeep.
4. Determine prohibited frequency
There is a certain prohibited frequency such as a power supply frequency.
For Cooling Only Model
1. Determine command frequency
Command frequency will be determined in the following order of priority.
1.1 Limiting frequency by drooping function
Input current, discharge pipes, freeze-up protection, dew prevention, fin thermistor temperature.
1.2 Indoor frequency command
Command frequency
Limit frequency
Skip control
Upper limit function
Compressor protection function
Lower limit function
Four-way valve operating compensation, etc. (*)
Initial frequency
PI control
Defrost control (*)
Drooping function
Input current control, etc.
Upper limit frequency
FMAX
Lower limit frequency
FMIN
Target frequency
Frequency changes by PI control < repeats when frequency becomes lower
Command frequency X repeats when frequency becomes lower
* only for heat pump model
(R2831)
Содержание FTKS20DVMW(L)
Страница 10: ...SiENBE04 507A List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 16: ...SiENBE04 507A Specifications 7 Part 2 Specifications 1 Specifications 8 1 1 Cooling Only 8 1 2 Heat Pump 21...
Страница 53: ...Printed Circuit Board Connector Wiring Diagram SiENBE04 507A 44 Printed Circuit Board Connector Wiring Diagram...
Страница 85: ...Control Specification SiENBE04 507A 76 Function and Control...
Страница 159: ...Check SiENBE04 507A 150 Service Diagnosis...
Страница 198: ...SiENBE04 507A Outdoor Unit Removal Procedure 189 When reassembling make sure to fit the hook Step Procedure Points Hook...
Страница 212: ...SiENBE04 507A Others 203 Part 8 Others 1 Others 204 1 1 Test Run from the Remote Controller 204 1 2 Jumper Settings 205...
Страница 215: ...Others SiENBE04 507A 206 Others...
Страница 221: ...Wiring Diagrams SiENBE04 507A 212 Appendix...
Страница 225: ...SiENBE04 507A iv Index...