SiENBE04-507A
Troubleshooting
Service Diagnosis
139
4.22 Output Over Current Detection
Remote
Controller
Display
L5
Method of
Malfunction
Detection
An output over-current is detected by checking the current that flows in the inverter DC section.
Malfunction
Decision
Conditions
A position signal error occurs while the compressor is running.
A speed error occurs while the compressor is running.
An output over-current input is fed from the output over-current detection circuit to the
microcomputer.
The system will be shut down if the error occurs 255 times.
Clearing condition: Continuous run for about 10 minutes (normal)
Supposed
Causes
Over-current due to defective power transistor
Over-current due to wrong internal wiring
Over-current due to abnormal supply voltage
Over-current due to defective PCB
Error detection due to defective PCB
Over-current due to closed stop valve
Over-current due to compressor failure
Over-current due to poor installation condition
Содержание FTKS20DVMW(L)
Страница 10: ...SiENBE04 507A List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 16: ...SiENBE04 507A Specifications 7 Part 2 Specifications 1 Specifications 8 1 1 Cooling Only 8 1 2 Heat Pump 21...
Страница 53: ...Printed Circuit Board Connector Wiring Diagram SiENBE04 507A 44 Printed Circuit Board Connector Wiring Diagram...
Страница 85: ...Control Specification SiENBE04 507A 76 Function and Control...
Страница 159: ...Check SiENBE04 507A 150 Service Diagnosis...
Страница 198: ...SiENBE04 507A Outdoor Unit Removal Procedure 189 When reassembling make sure to fit the hook Step Procedure Points Hook...
Страница 212: ...SiENBE04 507A Others 203 Part 8 Others 1 Others 204 1 1 Test Run from the Remote Controller 204 1 2 Jumper Settings 205...
Страница 215: ...Others SiENBE04 507A 206 Others...
Страница 221: ...Wiring Diagrams SiENBE04 507A 212 Appendix...
Страница 225: ...SiENBE04 507A iv Index...