Error Codes
ESIE05-04
3–36
Part 3 – Troubleshooting
3
1
3
4
5
2.5
Indoor Unit Fan Motor Lock (
A6
)
Error code
A6
LED indications
The table below shows the LED indications.
Error generation
The error is generated when the fan rotations are not detected while the output voltage to the fan is at
its maximum.
Causes
The possible causes are:
Q
Malfunctioning indoor unit fan motor
Q
Broken or disconnected wire
Q
Malfunctioning contact
Q
Malfunctioning indoor unit PCB.
Operation
HAP (green)
HBP (green)
Normal
c
c
Malfunctioning
c
c