Test Run and Operation Data
ESIE05-04
4–26
Part 4 – Commissioning and Test Run
3
1
4
5
Correlation of
Air-Conditioner’s
Operation Status
and Pressure /
Running Current
What happens in comparison to normal values is summarized in the table below.
(Measured from 15 ~ 20 minutes or more after operation starts.)
When Cooling
When Heating
Notes:
Q
∗
1. Water in the refrigerant freezes inside the capillary tube or expansion valve, and is basically
the same phenomenon as pump down.
Q
∗
2. Dirt in the refrigerant clogs filters inside the piping, and is basically the same phenomenon as
pump down.
Q
∗
3. Pressure differential between high and low pressure becomes low.
Air-Conditioner Status
Low Pressure
High Pressure
Running Current
Air Filter Fouling
Lower
Lower
Lower
Short Circuit of Indoor Unit
Inlet/Outlet Air
Lower
Lower
Lower
Outdoor Unit Fin Fouling
Higher
Higher
Higher
Short Circuit of Outdoor Unit
Inlet/Outlet Air
Higher
Higher
Higher
Air Mixed in Refrigerant
Higher
Higher
Higher
Water Mixed in Refrigerant
∗
1 Lower
Lower
Lower
Dirt Mixed in Refrigerant
∗
2 Lower
Lower
Lower
Lack of Refrigerant (Gas)
Lower
Lower
Lower
Unsatisfactory Compression
∗
3 Higher
Lower
Lower
Air-Conditioner Status
Low Pressure
High Pressure
Running Current
Air Filter Fouling
Higher
Higher
Higher
Short Circuit of Indoor Unit
Inlet/Outlet Air
Higher
Higher
Higher
Outdoor Unit Fin Fouling
Lower
Lower
Lower
Short Circuit of Outdoor Unit
Inlet/Outlet Air
Lower
Lower
Lower
Air Mixed in Refrigerant
Higher
Higher
Higher
Water Mixed in Refrigerant
∗
1 Lower
Lower
Lower
Dirt Mixed in Refrigerant
∗
2 Lower
Lower
Lower
Lack of Refrigerant (Gas)
Lower
Lower
Lower
Unsatisfactory Compression
∗
3 Higher
Lower
Lower
Содержание FHQ100BUV3B
Страница 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Страница 2: ......
Страница 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Страница 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Страница 78: ...ESIE05 04 1 60 Part 1 System Outline...
Страница 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Страница 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Страница 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Страница 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Страница 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Страница 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Страница 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...