ESIE05-04
Functional concept
Part 2 – Functional Description
2–9
3
2
4
5
1
1.6
Restart Standby
Outline
To prevent the compressor from frequently turning ON and OFF and allow pressure equalization,
forced thermostat OFF will be conducted for 3 minutes after compressor stopping (compressor guard
timer).
Graph
Thermostat OFF
Compressor
Electronic expansion valve
Oudoor unit fan
ON
ON
OFF
OFF
OFF
Restart standby
complete
Residual
operation
For 3 minutes
Moves to “Stop” or
“Starting control” after
completion of “Restart
standby”.