9
|
Electrical installation
Installer reference guide
146
ERRA08~12E + ELVH/23E
Daikin Altherma 3 R MT F
4P708474-1 – 2023.05
3
Connect the changeover to external heat source cable to the appropriate
terminals as shown in the illustration below.
A
X1
X2
L
N
B
A
B
A4P
X2M
X1
a
X2
a
Installation of EKRP1HBAA is required.
4
Fix the cable with cable ties to the cable tie mountings.
9.3.9 To connect the power consumption digital inputs
Wires: 2 (per input signal)×0.75 mm²
Power limitation digital inputs: 12 V DC / 12 mA detection (voltage
supplied by PCB)
[9.9]
Power consumption control
.
1
"7.2.2 To open the outdoor unit"
78].
2
"7.2.6 To open the indoor unit"
81]):
1
Top panel
1
2
3
2
User interface panel
3
Upper switch box cover
3
Connect the power consumption digital inputs cable to the appropriate
terminals as shown in the illustration below.