3
|
Specific installer safety instructions
Installer reference guide
17
ERRA08~12E + ELVH/23E
Daikin Altherma 3 R MT F
4P708474-1 – 2023.05
CAUTION
Install the indoor unit at a minimum distance of 1 m from other heat sources (>80°C)
(e.g. electrical heater, oil heater, chimney) and combustible materials. Otherwise the
unit may be damaged or in extreme cases catch fire.
Special requirements for R32 (see
"7.1.1 Installation site requirements of the
)
WARNING
▪
Do NOT pierce or burn refrigerant cycle parts.
▪
Do NOT use means to accelerate the defrosting process or to clean the
equipment, other than those recommended by the manufacturer.
▪
Be aware that R32 refrigerant does NOT contain an odour.
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well-
ventilated room without continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric heater) and have a room
size as specified below.
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions
from Daikin and with applicable legislation and are executed ONLY by authorised
persons.
WARNING
For units using the R32 refrigerant it is necessary to keep any required ventilation
openings and chimneys clear of obstructions.
Opening and closing the units (see
"7.2 Opening and closing the units"
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
Mounting the outdoor unit (see
"7.3 Mounting the outdoor unit"
WARNING
Fixing method of the outdoor unit MUST be in accordance with the instructions from
this manual. See
"7.3 Mounting the outdoor unit"
84].
CAUTION
To avoid injury, do NOT touch the air inlet or aluminium fins of the unit.