WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
9.1.2 Guidelines when connecting the electrical wiring
NOTICE
We recommend using solid (single-core) wires. If stranded wires are used, slightly
twist the strands to consolidate the end of the conductor for either direct use in the
terminal clamp or insertion in a round crimp-style terminal.
To prepare stranded conductor wire for installation
Method 1: Twisting conductor
1
Strip insulation (20 mm) from the wires.
2
Slightly twist the end of the conductor to create a "solid-like" connection.
Method 2: Using round crimp-style terminal
1
Strip insulation from wires and slightly twist the end of each wire.
2
Install a round crimp-style terminal on the end of the wire. Place the round
crimp-style terminal on the wire up to the covered part and fasten the
terminal with the appropriate tool.
Use the following methods for installing wires:
Wire type
Installation method
Single-core wire
Or
Stranded conductor wire
twisted to "solid-like"