9
|
Electrical installation
Installer reference guide
127
ERRA08~12E + ELVH/23E
Daikin Altherma 3 R MT F
4P708474-1 – 2023.05
9.2.2 To connect the electrical wiring to the outdoor unit
NOTICE
▪
Follow the wiring diagram (delivered with the unit, located at the inside of the
service cover).
▪
Make sure the electrical wiring does NOT obstruct proper reattachment of the
service cover.
1
Open the service cover. See
"7.2.2 To open the outdoor unit"
2
Strip insulation (20 mm) from the wires.
a
b
a
Strip wire end to this point
b
An excessive strip length may cause electrical shock or leakage
3
Insert the cables at the back of the unit, and route them through the factory-
mounted cable sleeves into the switch box.
a1+a2
Power supply cable (field supply)
b1+b2
Interconnection cable (field supply)
c1+c2
No use
d
Cable sleeves (factory-mounted)
4
Inside the switch box, connect the wires to the appropriate terminals, and fix
the cables with cable ties. See:
▪
▪
In case of V3 models
1
Power supply cable
:
▪
Route the cable through the frame.
▪
Connect the wires to the terminal block.
▪
Fix the cable with a cable tie.
Wires: 1N+GND
Maximum running current: Refer to name plate on unit.