Outline of Control
Function
47
6.4
Low Outdoor Air Temperature Protection Control
Objective
In cooling (or fan operation) or heating, if outdoor air is low in temperature, stop the fan forcibly.
Details
[Cooling and fan operation]
Turn OFF the fan for a period of 60 minutes at a suction temperature of 5 C or lower.
In order to monitor the outdoor air temperature, however, turn ON the fan for a period of one
minute and turn OFF the fan again at a temperature of 5 C or lower after the said timer
completes the operative period.
Reset the 60-minute timer when the fan stops running.
[Heating]
Turn OFF the fan for a period of 60 minutes at a suction temperature of –5 C or lower.
In order to monitor the outdoor air temperature, however, turn ON the fan for a period of one
minute and turn OFF the fan again at a temperature of –5 C or lower after the said timer
completes the operative period.
Reset the 60-minute timer when the fan stops running.
* The thermostat will not turn ON in one minute due to the temperature while the fan stops.
This control shall be disabled at test run both in cooling and heating. (The test run shall be
conducted first.)
Содержание ERQ Series
Страница 2: ......
Страница 16: ...Combination Table ESiEN09 06 A 6 General Information...
Страница 17: ...ESiEN09 06 A Specifications 7 1 Specifications 8 1 1 Outdoor Units 8...
Страница 33: ...ESiEN09 06 A Function general Function 23 1 2 Operation Mode...
Страница 58: ...Outline of Control ESiEN09 06 A 48 Function...
Страница 70: ...Wiring Diagram of Control Box ESiEN09 06 A 60 Control Box EKEQ CBV3 3 Wiring Diagram of Control Box 3 1 D box...
Страница 71: ...ESiEN09 06 A Wiring Diagram of Control Box Control Box EKEQ CBV3 61 3 2 F box...
Страница 109: ...Test Operation ESiEN09 06 A 100 Test Operation 1 2 2 Turn power on...