Field Setting
ESiEN09-06 A
120
Test Operation
Heating
T
c
target:
INITIAL VALUE BASE ON ZONE
Adjustable by:
(6.2) X-control
Cooling: Upper & lower limit of T
e
can be chosen
Correction field setting 21-2 (-1 ~ +2°C)
W-control
Setting
Description
Operation mode
01
02
03
04
Correction target T
c
21-2
0
+1
+2
-1
Mode n° setting
Setting switch n° Setting position n°
Setting
Lower limit T
e
(°C)
Upper limit T
e
(°C)
51
1
00
-7
20
01
-3
20
02
0
20
03
3
20
04
-7
15
05
-3
15
06
0
15
07
3
15
08
-7
10
09
-3
10
10
0
10
11
3
10
12
-7
8
13
-3
8
14
0
8
15
3
8