ESiEN09-06 A
Special Control
Function
31
3.2.2 Oil Return Operation in Heating Operation
Outdoor Unit Actuator
Oil return preparation
operation
Oil return operation
Post-oil-return operation
Compressor
Upper limit control
176 Hz + ON + ON
124 Hz + OFF + OFF
2-steps increase/20sec.
till Pc - Pe>0.4 MPa
Outdoor unit fan
STEP7
or
STEP8
OFF
STEP8
Four way valve
ON
OFF
ON
Main motorized valve (EV1)
SH control
480 pls
480 pls
55 pls
Subcooling motorized valve (EV2)
SH control
0 pls
0 pls
Hot gas bypass valve (SVP)
OFF
OFF
OFF
Accumulator oil return valve (SVO)
ON
ON
ON
Injection (SVT) (RXYQ5P model only)
OFF
OFF
OFF
Ending conditions
170 sec.
4 min.
Ts - Te<5 C
10 sec.
Pc - Pe>0.4MPa
or
or
AHU actuator
Heating oil return operation
Fan
Thermostat ON unit
Field setting
Stopping unit
OFF