
Test Operation
ESiEN09-06 A
102
Test Operation
1.2.3.2
Air Tight Test and Vacuum Drying Method
After finished piping work, carry out air tight test and vacuum drying.
<Air tight test>
Pressurize the liquid and gas pipes to 4.0MPa (40bar) (do not pressurize more than 4.0MPa
(40bar)). If the pressure does not drop within 24 hours, the system passes the test.
If there is a pressure drop, check for leaks, make repairs, and perform the airtight test again.
<Vacuum drying>
Evacuate the system from the liquid and gas pipes by using a vacuum pump for more than 2
hours and bring the system to –100.7kPa or less. After keeping the system under that condition
for more than 1 hour, check if the vacuum gauge rises or not. If it rises, the system may either
contain moisture inside or have leaks.
Note:
If moisture might enter the piping, follow belows.
(I.e., if doing work during the rainy season, if the actual work takes long enough that
condensation may form on the inside of the pipes, if rain might enter the pipes during
work, etc.)
1. After performing the vacuum drying for two hours, pressurize to 0.05 MPa (i.e., vacuum
breakdown) with nitrogen gas, then depressurize down to –100.7 kPa for an hour using the
vacuum pump (vacuum drying).
2. If the pressure does not reach –100.7 kPa even after depressurizing for at least two hours,
repeat the vacuum breakdown - vacuum drying process.
After vacuum drying, maintain the vacuum for an hour and make sure the pressure does not rise
by monitoring with a vacuum gauge.
1.2.4 Additional Refrigerant Charge and Check Operation
Maximum piping length is 55 m. For calculation of additional refrigerant charge, we refer to the
installation manual.
1.2.4.1
Before Working
[About the refrigerant cylinder]
Check whether the cylinder has a siphon pipe before charging and place the cylinder so that the
refrigerant is charged in liquid form. (See the figure below.)
Caution
Always use the proper refrigerant (R-410A). If charged with the refrigerant containing an
improper material, it may cause an explosion or accident.
R-410A is a mixed refrigerant, so charging it as a gas will cause the refrigerant composition
to change, which may prevent normal operation.
With siphon pipe
Other tanks
Stand the cylinder upright and charge.
(The siphon pipe goes all the way inside,
so the cylinder does not need be put
upside-down charge in liquid form.)
Stand the cylinder upside-down and charge.
Содержание ERQ Series
Страница 2: ......
Страница 16: ...Combination Table ESiEN09 06 A 6 General Information...
Страница 17: ...ESiEN09 06 A Specifications 7 1 Specifications 8 1 1 Outdoor Units 8...
Страница 33: ...ESiEN09 06 A Function general Function 23 1 2 Operation Mode...
Страница 58: ...Outline of Control ESiEN09 06 A 48 Function...
Страница 70: ...Wiring Diagram of Control Box ESiEN09 06 A 60 Control Box EKEQ CBV3 3 Wiring Diagram of Control Box 3 1 D box...
Страница 71: ...ESiEN09 06 A Wiring Diagram of Control Box Control Box EKEQ CBV3 61 3 2 F box...
Страница 109: ...Test Operation ESiEN09 06 A 100 Test Operation 1 2 2 Turn power on...