Piping installation
Installer reference guide
84
ERGA04~08EA + 08S18+23EA
Daikin Altherma 3 R F
4P629093-1A – 2021.11
▪
Closed circuit.
Use the indoor unit ONLY in a closed water system. Using the
system in an open water system will lead to excessive corrosion.
▪
Glycol.
For safety reasons, it is NOT allowed to add any kind of glycol to the
water circuit.
▪
Piping length.
It is recommended to avoid long runs of piping between the
domestic hot water tank and the hot water end point (shower, bath,…) and to
avoid dead ends.
▪
Piping diameter.
Select the water piping diameter in relation to the required
water flow and the available external static pressure of the pump. See
243] for the external static pressure curves of the indoor
unit.
▪
Water flow.
You can find the minimum required water flow for indoor unit
operation in the following table. In all cases, this flow needs to be guaranteed.
When the flow is lower, the indoor unit will stop operation and display error 7H.
Minimum required flow rate
12 l/min
▪
Field supply components – Water.
Only use materials that are compatible with
water used in the system and with the materials used in the indoor unit.
▪
Field supply components – Water pressure and temperature.
Check that all
components in the field piping can withstand the water pressure and water
temperature.
▪
Water pressure – Domestic hot water.
The maximum water pressure is 4 bar.
Provide adequate safeguards in the water circuit to ensure that the maximum
pressure is NOT exceeded. The minimum water pressure to operate is 1 bar.
▪
Water pressure –
Space heating/cooling circuit.
The maximum water pressure is
3 bar. Provide adequate safeguards in the water circuit to ensure that the
maximum pressure is NOT exceeded. The minimum water pressure to operate is
1 bar.
▪
Water temperature.
All installed piping and piping accessories (valve,
connections,…) MUST withstand the following temperatures:
INFORMATION
The following illustration is an example and might NOT match your system layout.
89°C
75°C
M
M
a
b c d
g
e
h
i
i
i
j
j
f
k
i
HPC1
FHL1
FHL2 FHL3
HPC2
HPC3