9
|
Electrical installation
Installer reference guide
111
ERGA04~08EA + 08S18+23EA
Daikin Altherma 3 R F
4P629093-1A – 2021.11
B
A
B
7 9
X2M
A4P
Y1
YC
X1M
a
b
a
Installation of EKRP1HBAA (+ mounting plate, see
b
Prewiring between X2M/7+9 and Q1L (= thermal protector backup heater). Do NOT
change.
3
Fix the cable with cable ties to the cable tie mountings.
9.3.7 To connect the space cooling/heating ON/OFF output
Wires: (2+1)×0.75 mm²
Maximum load: 0.3 A, 250 V AC
—
1
Open the following (see
"7.2.4 To open the indoor unit"
1
Top panel
1
2
3
2
User interface panel
3
Upper switch box cover
2
Connect the space cooling/heating ON/OFF output cable to the appropriate
terminals as shown in the illustration below.
7 9
YC
Y2
X2M
1
2
3
A4P
1+2
Wires connected to the space
cooling/heating ON/OFF output
3
Wire between X2M and A4P
A4P
Installation of EKRP1HBAA is
required.