14
|
Troubleshooting
Installer reference guide
235
ERGA04~08EA + 08S18+23EA
Daikin Altherma 3 R F
4P629093-1A – 2021.11
Possible causes
Corrective action
The backup heater equilibrium
temperature has not been configured
correctly
Increase the equilibrium temperature to
activate the backup heater operation at
a higher outdoor temperature.
Go to: [9.3.7]:
Installer settings
>
Backup heater
>
Equilibrium
temperature
[5‑01]
There is air in the system.
Purge air manually or automatically. See
the air purge function in the chapter
211].
Too much heat pump capacity is used
for heating domestic hot water
Check if the
Space heating
priority
settings have been
configured appropriately:
▪
Make sure that the
Space heating
priority
has been enabled.
Go
to
[9.6.1]:
Installer
settings
>
Balancing
>
Space
heating priority
[5‑02]
▪
Increase the "space heating priority
temperature" to activate backup
heater operation at a higher outdoor
temperature.
Go
to
[9.6.3]:
Installer
settings
>
Balancing
>
Priority temperature
[5‑03]
14.3.9 Symptom: The pressure at the tapping point is temporarily unusually high
Possible causes
Corrective action
Failing or blocked pressure relief valve.
▪
Flush and clean the complete tank
including the piping between pressure
relief valve and the cold water inlet.
▪
Replace the pressure relief valve.
14.3.10 Symptom: Decoration panels are pushed away due to a swollen tank
Possible causes
Corrective action
Failing or blocked pressure relief valve.
Contact your local dealer.
14.3.11 Symptom: Tank disinfection function is NOT completed correctly (AH-error)
Possible causes
Corrective action
The disinfection function was
interrupted by domestic hot water
tapping
Program the start-up of the disinfection
function when the coming 4 hours NO
domestic hot water tapping is expected.