7/10
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.I
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.I
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.I
[2-0E]
R/W
0~50 A, step: 1 A
50 A
9.I
[3-00]
R/W
0: No
1: Yes
9.I
[3-01]
0
9.I
[3-02]
1
9.I
[3-03]
4
9.I
[3-04]
2
9.I
[3-05]
1
9.I
[3-06]
R/W
18~30°C, step: 1°C
30°C
9.I
[3-07]
R/W
12~18°C, step: 1°C
12°C
9.I
[3-08]
35
9.I
[3-09]
15
9.I
[4-00]
R/W
0: Disabled
1: Enabled
2: Only DHW
9.I
[4-01]
R/W
0: None
1: BSH
2: BUH
9.I
[4-02]
R/W
14~35°C, step: 1°C
2
2°C
9.I
[4-03]
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
9.I
[4-04]
0: Intermittent
1: Continuous
2: Off
9.I
[4-05]
0
9.I
[4-06]
R/W
0: Manual
1: Automatic(normal SH/DHW ON)
2: Auto red SH/DHW ON
3: Auto red SH/DHW OFF
4: SH ON/DHW OFF
9.I
[4-07]
6
9.I
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
9.I
[4-09]
R/W
0: Current
1: Power
9.I
[4-0A]
R/W
0: 1 (*1)
1: 1/1+2 (*2) (*3)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.I
[4-0B]
1
9.I
[4-0D]
3
9.I
[4-0E]
6
9.I
[5-00]
R/W
0: No
1: Yes
9.I
[5-01]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-02]
R/W
0: Disabled
1: Enabled
9.I
[5-03]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-04]
R/W
0~20°C, step: 1°C
10°C
9.I
[5-05]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-06]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-07]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-08]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0A]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0B]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0C]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0D]
R/W (*2)
R/O (*1)
(*3)
0: 230V, 1~ (*1) (*2)
1: 230V, 3~ (*2)
2: 400V, 3~ (*3)
9.I
[5-0E]
1
9.I
[6-00]
R/W
2~40°C, step: 1°C
25°C
9.I
[6-01]
R/W
0~10°C, step: 1°C
2°C
9.I
[6-02]
R/W
0~10kW, step: 0,2kW
0
kW
9.I
[6-03]
R/W
0~10kW, step: 0,2kW
2
kW (*2)
3kW (*1)(*3)
9.I
[6-04]
R/O (*1)
R/W (*2)
(*3)
0~10kW, step: 0,2kW
0kW (*1)
4kW (*2)
6kW (*3)
9.I
[6-05]
0
9.I
[6-06]
0
9.I
[6-07]
R/W
0~200W, step: 10W
0W
--
--
--
What is the maximum desired room temperature in heating?
Below which outdoor temperature is heating allowed?
What is the requested limit for DI4?
What is the equilibrium temperature for the building?
What is the requested limit for DI2?
What is the requested limit for DI3?
Space heating priority temperature.
Set point correction for domestic hot water temperature.
What is the requested limit for DI1?
--
The temperature difference determining the heat pump ON temperature.
The temperature difference determining the heat pump OFF temperature.
What is the capacity of the booster heater?
What is the capacity of the backup heater step 1?
What is the capacity of the backup heater step 2?
Water pipe freeze prevention
Space heating priority.
What is the mimimum desired room temperature in heating?
What is the BUH operation mode?
Which electric heater has priority?
Which power limitation mode is required on the system?
--
Emergency
--
What emitter type is connected to the main LWT zone?
What is the requested limit for DI4?
Equilibrium: Deactivate backup heater (or external backup heat source in case of a
bivalent system) above the equilibrium temperature for space heating?
Which power limitation type is required?
--
What is the requested limit for DI1?
--
What is the capacity of the bottom plate heater?
--
--
Backup heater voltage
What is the requested limit for DI2?
What is the requested limit for DI3?
Backup heater configuration
Operation permission of the booster heater.
--
--
Is auto restart of the unit allowed?
--
What is the maximum allowed current over the heatpump ?
--
--
What emitter type is connected to the additional LWT zone?
(*1) *3V_
(*2) *6V_
(*3) *9W
(#) Setting is not applicable for this unit.