3/10
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
Additional zone
3.7
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└─ Setpoint range
3.8.1
[9-05]
R/W
15~37°C, step: 1°C
25°C
3.8.2
[9-06]
R/W
[2-0D]=2:
37~65, step: 1°C
55°C
[2-0D]≠2:
37~55, step: 1°C
55°C
3.8.3
[9-07]
R/W
5~18°C, step: 1°C
5°C
3.8.4
[9-08]
R/W
18~22°C, step: 1°C
22°C
Additional zone
3.A
[C-06]
R/W
0: -
1: 1 contact
2: 2 contacts
└─ Delta T
3.B.1
[1-0C]
R/W
3~10°C, step: 1°C
5°C
3.B.2
[1-0E]
R/W
3~10°C, step: 1°C
5°C
Space heating / cooling
└─ Operation range
4.3.1
[4-02]
R/W
14~35°C, step: 1°C
2
2°C
4.3.2
[F-01]
R/W
10~35°C, step: 1°C
20°C
Space heating / cooling
4.4
[7-02]
R/W
0: 1 LWT zone
1: 2 LWT zones
4.5
[F-0D]
R/W
0: Continuous
1: Sample
2: Request
4.6
[E-02]
R/W (*6)
R/O (*7)
0: Reversible (*6)
1: Heating only (*7)
4.7
[9-0D]
R/W
0~8, step:1
0 : No limitation
1~4 : 50~80%
5~8 : 50~80% during sampling
6
Space heating / cooling
4.9
[F-00]
R/W
0: Restricted
1: Allowed
4.A
[D-03]
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
4.B
[9-04]
R/W
1~4°C, step: 1°C
1°C
4.C
[2-06]
R/W
0: Disabled
1: Enabled
Tank
5.2
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
5.3
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
5.4
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
5.6
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
└─ Disinfection
5.7.1
[2-01]
R/W
0: No
1: Yes
5.7.2
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
5.7.3
[2-02]
R/W
0~23 hour, step: 1 hour
1
5.7.4
[2-03]
R/W
[E-07]≠
1 :
55~75°C, step: 5°C
70°C
[E-07]=1 : 60°C
60°C
5.7.5
[2-04]
R/W
[E-07]≠1: 5~60 min, step: 5 min
10 min
[E-07]=1: 40~60 min, step: 5 min
40 min
Tank
5.8
[6-0E]
R/W
(*4) : 40~75°C, step: 1°C
60°C
[E-07]=0
(*4) : 40~80°C, step: 1°C
80°C
[E-07]=5
(*5) : 40~60°C, step: 1°C
60°C
5.9
[6-00]
R/W
2~40°C, step: 1°C
25°C
5.A
[6-08]
R/W
2~20°C, step: 1°C
10°C
5.B
R/W
0: Fixed
1: Weather dependent
Operation day
Hysteresis
Overshoot
Duration
Tank setpoint
Hysteresis
Comfort setpoint
Delta T heating
Space heating OFF temp
Pump limitation
Number of zones
Unit type
Increase around 0°C
Cooling minimum
Cooling maximum
Space cooling OFF temp
Thermostat type
Emitter type
Heating minimum
Heating maximum
Delta T cooling
Start time
Pump outside range
Setpoint mode
Maximum
Heat up mode
Reheat setpoint
Eco setpoint
Pump operation mode
Antifrost
Activation
(*1) *3V_(*2) *6V_
(*3) *9W_(*4) *HB*_
(*5) EHV*_
(*6) *X*_(*7) *H*
(#) Setting is not applicable for this unit.