9/10
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
9.I
[8-07]
R/W
[9-03]~[9-02], step: 1°C
18°C
9.I
[8-08]
R/W
[9-03]~[9-02], step: 1°C
20°C
9.I
[8-09]
R/W
[9-01]~[9-00], step: 1°C
35°C
9.I
[8-0A]
R/W
[9-01]~[9-00], step: 1°C
33°C
9.I
[8-0B]
13
9.I
[8-0C]
10
9.I
[8-0D]
16
9.I
[9-00]
R/W
[2-0C]=2:
37~65, step: 1°C
55°C
[2-0C]≠2:
37~55, step: 1°C
55°C
9.I
[9-01]
R/W
15~37°C, step: 1°C
25°C
9.I
[9-02]
R/W
18~22°C, step: 1°C
22°C
9.I
[9-03]
R/W
5~18°C, step: 1°C
5°C
9.I
[9-04]
R/W
1~4°C, step: 1°C
1°C
9.I
[9-05]
R/W
15~37°C, step: 1°C
25°C
9.I
[9-06]
R/W
[2-0D]=2:
37~65, step: 1°C
55°C
[2-0D]≠2:
37~55, step: 1°C
55°C
9.I
[9-07]
R/W
5~18°C, step: 1°C
5°C
9.I
[9-08]
R/W
18~22°C, step: 1°C
22°C
9.I
[9-0C]
R/W
1~6°C, step: 0,5°C
1 °C
9.I
[9-0D]
R/W
0~8, step:1
0 : No limitation
1~4 : 50~80%
5~8 : 50~80% during sampling
6
9.I
[9-0E]
6
9.I
[C-00]
R/W
0: Solar priority
1: Heat pump priority
9.I
[C-01]
0
9.I
[C-02]
R/W
0: No
1: Bivalent
9.I
[C-03]
R/W
-25~25°C, step: 1°C
0°C
9.I
[C-04]
R/W
2~10°C, step 1°C
3°C
9.I
[C-05]
R/W
0: -
1: 1 contact
2: 2 contacts
9.I
[C-06]
R/W
0: -
1: 1 contact
2: 2 contacts
9.I
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
9.I
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
9.I
[C-09]
R/W
0: Normally open
1: Normally closed
9.I
[C-0A]
0
9.I
[D-00]
R/W
0: None
1: BSH only
2: BUH only
3: All heaters
9.I
[D-01]
R/W
0: No
1: Active open
2: Active closed
3: Safety thermostat
9.I
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
9.I
[D-03]
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
9.I
[D-04]
R/W
0: No
1: Pwr consmp ctrl
9.I
[D-05]
R/W
0: Forced off
1: As normal
9.I
[D-07]
R/W
0: No
1: Yes
9.I
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
9.I
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
What is the desired comfort main LWT in cooling?
What is the desired eco main LWT in cooling?
What is the desired comfort main LWT in heating?
What is the desired eco main LWT in heating?
--
--
--
What is the maximum desired LWT for main zone in heating?
What is the mimimum desired LWT for main zone in heating?
What is the maximum desired LWT for main zone in cooling?
What is the mimimum desired LWT for main zone in cooling?
Leaving water temperature overshoot temperature.
What is the mimimum desired LWT for add. zone in heating?
What is the maximum desired LWT for add. zone in heating?
What is the mimimum desired LWT for add. zone in cooling?
What is the maximum desired LWT for add. zone in cooling?
Room temperature hysteresis.
Pump speed limitation
--
Domestic heating water priority.
--
Is an external backup heat source connected?
Bivalent activation temperature.
Bivalent hysteresis temperature.
What is the thermo request contact type for the main zone?
Which heaters are permitted if prefer. kWh rate PS is cut?
Contact type of preferential kWh rate PS installation?
Which type of DHW pump is installed?
Leaving water temperature compensation around 0°C.
What is the thermo request contact type for the add. zone?
What is the unit control method in space operation?
Which type of external sensor is installed?
What is the required alarm output contact type?
--
Is a demand PCB connected?
Is the pump allowed to run if prefer. kWh rate PS is cut?
Is a solar kit connected?
Is an external kWh meter used for power measurement?
Is an external kWh meter used for power measurement?
(*1) *3V_(*2) *6V_
(*3) *9W_(*4) *HB*_
(*5) EHV*_
(*6) *X*_(*7) *H*
(#) Setting is not applicable for this unit.