7 Installation
Installer reference guide
40
ERGA04~08DAV3(A) + EHVH/X04+08S18+23DA
Daikin Altherma – Low temperature split
4P495248-1 – 2017.12
4
Reattach the top panel.
7.8.5
To connect the drain hose to the drain
Water coming from the pressure relief valve is collected in the drain
pan. The drain pan is connected to a drain hose inside the unit. You
must connect the drain hose to an appropriate drain according to the
applicable legislation. You can route the drain hose through the left
or right side panel.
Prerequisite:
The user interface panel and front panel have been
removed.
1
Remove one of the side panels.
2
Cut out the rubber grommet.
3
Pull the drain hose through the hole.
4
Reattach the side panel. Ensure the water can flow through the
drain tube.
It is recommended to use a tundish to collect the water.
Option 1: Through the left side panel
1
3×
T25
3
2
Option 2: Through the right side panel
1
3×
T25
3
2
7.8.6
To fill the water circuit
To fill the water circuit, use a field supply filling kit. Make sure you
comply with the applicable legislation.
INFORMATION
Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.
7.8.7
To fill the domestic hot water tank
1
Open every hot water tap in turn to purge air from the system
pipe work.
2
Open the cold water supply valve.
3
Close all water taps after all air is purged.
4
Check for water leaks.
5
Manually operate the field-installed pressure relief valve to
ensure a free water flow through the discharge pipe.
7.8.8
To insulate the water piping
The piping in the complete water circuit MUST be insulated to
prevent condensation during cooling operation and reduction of the
heating and cooling capacity.
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, the thickness of the insulation materials should be at
least 20 mm to prevent condensation on the surface of the
insulation.
7.9
Connecting the electrical wiring
7.9.1
About connecting the electrical wiring
Before connecting the electrical wiring
Make sure:
▪ The refrigerant piping is connected and checked
▪ The water piping is connected
Final English - Tanslations in progress