7 Installation
Installer reference guide
33
ERGA04~08DAV3(A) + EHVH/X04+08S18+23DA
Daikin Altherma – Low temperature split
4P495248-1 – 2017.12
b
a
c
a
Drain pan
b
U-beams
c
Drain hole insulation
355 mm
600 mm
▪
Drain pan heater.
You can use the drain pan heater option
(EKDPH008CA) to prevent freezing-up of the drain pan. For the
installation instructions, see the installation manual of the drain
pan heater.
▪
Non-heated drain tube.
When using the drain pan heater without
drain tube or with a non-heated drain tube, remove the drain hole
insulation (Item c on the illustration).
7.3.6
To prevent the outdoor unit from falling
over
In case the unit is installed in places where strong wind can tilt the
unit, take following measure:
1
Prepare 2 cables as indicated in the following illustration (field
supply).
2
Place the 2 cables over the outdoor unit.
3
Insert a rubber sheet between the cables and the outdoor unit
to prevent the cable from scratching the paint (field supply).
4
Attach the cable’s ends. Tighten those ends.
7.4
Mounting the indoor unit
7.4.1
About mounting the indoor unit
When
You have to mount the outdoor and indoor unit before you can
connect the refrigerant and water piping.
Typical workflow
Mounting the indoor unit typically consists of the following stages:
1
Installing the indoor unit.
7.4.2
Precautions when mounting the indoor
unit
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
7.4.3
To install the indoor unit
1
Lift the indoor unit from the pallet and place it on the floor. Also
see
"3.3.3 To handle the indoor unit" on page 8
.
2
Connect the drain hose to the drain. See
"7.8.5 To connect the
drain hose to the drain" on page 40
.
3
Slide the indoor unit into position.
4
Adjust the height of the leveling feet to compensate for floor
irregularities. The maximum allowed deviation is 1°.
≤1°