Si18-525B
Troubleshooting for Outdoor Unit
Troubleshooting
387
7.21
Faulty Combination of Inverter and Fan Driver
Remote
Controller
Display
PJ
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Check the communication state between inverter PCB and control PCB by micro-computer.
Malfunction
Decision
Conditions
When the communication data about inverter PCB type is incorrect.
Supposed
Causes
Mismatching of inverter PCB
Faulty field setting
Troubleshooting
∗
Refer to “Field Setting from Outdoor Unit” on P166.
(Q0441)
After resetting, restart.
YES
YES
YES
Is the
PCB type
correct?
Is the field
setting when
the PCB was
replaced
correct?
Replace PCB by the correct one.
Replace the PCB.
NO
Was the PCB
replaced?
NO
Correct field setting.
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Содержание D-Series
Страница 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Страница 33: ...List of Functions Si18 525B 20 List of Functions ...
Страница 34: ...Si18 525B Specifications 21 Part 2 Specifications 1 Specifications 22 1 1 Cooling Only 22 1 2 Heat Pump 42 ...
Страница 71: ...Specifications Si18 525B 58 Specifications ...
Страница 107: ...Printed Circuit Board Connector Wiring Diagram Si18 525B 94 Printed Circuit Board Connector Wiring Diagram ...
Страница 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Страница 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Страница 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Страница 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Страница 443: ...BP Unit Si18 525B 430 Removal Procedure The clamps are to be kept in stock Step Procedure Points Clamps Q0529 ...
Страница 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Страница 475: ...Si18 525B vi Index ...