Field Setting
Si18-525B
180
Test Operation
3.2.3 Setting of
Refrigerant Recovery Mode
When carrying out the refrigerant collection on site, fully open the respective expansion valve of
BP and outdoor unit.
Both the outdoor unit and the indoor unit are forbidden to operation.
Operation
Procedure
In setting mode 2 with units in stop mode, set “B Refrigerant Recovery / Vacuuming mode”
to ON. The respective expansion valve of BP and outdoor units are fully opened. (H2P turns
to display “
” (test operation) (blinks), “
” (test operation)” and “
” (during contralized
control) are displayed on the remote controller (only for SkyAir), and the operation is
prohibited.
Collect the refrigerant using a refrigerant recovery unit. (See the instruction attached to the
refrigerant recovery unit for more detal.)
Press Mode button “BS1” once and reset “Setting Mode 2”.
3.2.4 Setting of
Vacuuming Mode
In order to perform vacuuming operation at site, fully open the expansion valves of BP and
outdoor units to turn on some solenoid valves.
Both the outdoor unit and the indoor unit are forbidden to operation.
Operating
procedure
With Setting Mode 2 while the unit stops, set (B) Refrigerant recovery / Vacuuming mode to
ON. The expansion valves of BP and outdoor units fully open and some of solenoid valves
open.
(H2P blinks to indicate the test operation, and the remote controller displays “
” (test
operation) and “
” (during contralized control) (only for SkyAir), thus prohibiting operation.)
After setting, do not cancel “Setting Mode 2” until completion of Vacuuming operation.
Use the vacuum pump to perform vacuuming operation.
Press Mode button “BS1” once and reset “Setting Mode 2”.
Содержание D-Series
Страница 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Страница 33: ...List of Functions Si18 525B 20 List of Functions ...
Страница 34: ...Si18 525B Specifications 21 Part 2 Specifications 1 Specifications 22 1 1 Cooling Only 22 1 2 Heat Pump 42 ...
Страница 71: ...Specifications Si18 525B 58 Specifications ...
Страница 107: ...Printed Circuit Board Connector Wiring Diagram Si18 525B 94 Printed Circuit Board Connector Wiring Diagram ...
Страница 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Страница 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Страница 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Страница 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Страница 443: ...BP Unit Si18 525B 430 Removal Procedure The clamps are to be kept in stock Step Procedure Points Clamps Q0529 ...
Страница 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Страница 475: ...Si18 525B vi Index ...