Si18-525B
Indoor Unit (SkyAir Models)
Function
151
2. Heating
2-1 Basic operation
2-1-1 When compressor stops during drain pump ON after compressor operation started
3
min
2-1-2 When compressor stops during drain pump OFF after compressor operation started
3
min
2-2
Operations when an occurrence of drain water level abnormality
2-2-a) Behavior between occurrence and recovery of drain water level abnormality
Drain pump
ON
OFF
ON
OFF
Compressor
ON
OFF
5min
20 min
5min
Compressor
ON
OFF
20 min
20 min
Drain pump
In heating operation of the unit equipped with a humidifier, when "Interlocking of drain pump /
humidifier" (15(25)-3) is set to "yes" (02), the drain pump operates 20-min OFF and 3-min ON
repeatedly during compressor is in operation.
After compressor stops, residual operation will be conducted for 5 minutes.
2-2-a)-1 When a water level abnormality occurs during drain pump ON
Occurrence of drain water level abnormality
5
sec
A
10
sec sec
Compressor
ON
OFF
Error processing
5min
Abnormal
Normal
Drain pan
Water level abnormality
Normal
Drain pump
ON
OFF
5min
Intermittent operation (*1)
After compressor stops due to water level abnormality, drain pump is operated intermittenly, i.e. 5 min
ON, 5 sec OFF and 5 min ON. (*1) The intermittent operation is executed regardless of recovery of abn.
Water level during the intermittent operation. (*2) When the abn. water level can not be recovered, the
latter 5 min ON operation is continued until recovery of the abnormality. (*3) On above diagram, the
system operation in the event of a water level abnormality occurrence differs between the drain pump ON
and OFF. The details are as follows.
1 The same operation as 1-2-a) "Behavior between occurrence and recovery of drain water level
abnormality" in the mode of cooling or dry.
*2
Even though the water level
abnormality could be recovered
during intermittent operation, the
operation shall be carried out
without exception.
*3
If the abnormality could not be recovered
during intermittent operation, the latter 5
min ON operation is continued until
recovery of the abnormality.
Note : ((2-2-a)-1 When a water level abnormality occurs during drain pump ON)
Recovery operation for drain water level abnormality does not activate when the water level can
be returned normal within A + 10 seconds.
Содержание D-Series
Страница 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Страница 33: ...List of Functions Si18 525B 20 List of Functions ...
Страница 34: ...Si18 525B Specifications 21 Part 2 Specifications 1 Specifications 22 1 1 Cooling Only 22 1 2 Heat Pump 42 ...
Страница 71: ...Specifications Si18 525B 58 Specifications ...
Страница 107: ...Printed Circuit Board Connector Wiring Diagram Si18 525B 94 Printed Circuit Board Connector Wiring Diagram ...
Страница 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Страница 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Страница 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Страница 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Страница 443: ...BP Unit Si18 525B 430 Removal Procedure The clamps are to be kept in stock Step Procedure Points Clamps Q0529 ...
Страница 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Страница 475: ...Si18 525B vi Index ...