Protection Control
Si18-525B
126
Function
4.6
Dew Condensation Prevention
Control
Outline
According to the dew condensation prevention status sent from the BP unit. The compressor
output frequency is regulated to decrease the compressor capacity in order to prevent the
indoor unit from dew condensation.
Detail
Zones are produced based on the dew condensation prevention status signal sent from the BP
unit (Indoor unit), and the dew condensation prevention control prevents dew condensation of
the indoor unit.
Recovery zone: Lift the control
Increase zone: 1 step up/60sec.
Keep zone: Frequency is not controlled
Decrease zone: 1 step down/60sec. SVG open at 52Hz
The temperature in above figure depends on models and actual room temperature. (Reference
value)
˚C
14.5
13
12.5
12
Recovery zone
Increase zone
Keep zone
Decrease zone
Indoor unit heat exchanger
temperature
Содержание D-Series
Страница 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Страница 33: ...List of Functions Si18 525B 20 List of Functions ...
Страница 34: ...Si18 525B Specifications 21 Part 2 Specifications 1 Specifications 22 1 1 Cooling Only 22 1 2 Heat Pump 42 ...
Страница 71: ...Specifications Si18 525B 58 Specifications ...
Страница 107: ...Printed Circuit Board Connector Wiring Diagram Si18 525B 94 Printed Circuit Board Connector Wiring Diagram ...
Страница 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Страница 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Страница 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Страница 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Страница 443: ...BP Unit Si18 525B 430 Removal Procedure The clamps are to be kept in stock Step Procedure Points Clamps Q0529 ...
Страница 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Страница 475: ...Si18 525B vi Index ...