Model Selection
SiUS39-601
4
General Information
3. Model Selection
VRV Heat Pump Series
Connectable Indoor Units Number and Capacity
Connectable Indoor Unit
Indoor Unit Capacity
Use the above tables to determine the capacities of indoor units to be connected. Make sure the
total capacity of indoor units connected to each outdoor unit is within the specified value (Btu/h).
The total capacity of connected indoor units must be within a range of 70 to 130% of the rated
capacity of the outdoor unit.
In some models, it is not possible to connect the maximum number of connectable indoor units.
Select models so the total capacity of connected indoor units conforms to the specification.
Ton
6 ton
8 ton
12 ton
14 ton
16 ton
System name
RXYQ72M
RXYQ96M
RXYQ144M
RXYQ168M
RXYQ192M
Outdoor unit 1
RXYQ72M
RXYQ96M
RXYQ72M
RXYQ72M
RXYQ96M
Outdoor unit 2
—
—
RXYQ72M
RXYQ96M
RXYQ96M
Total number of connectable indoor units
12
16
20
20
20
Total Capacity Index of Indoor Units to be Connected
50.5~93.5
67.5~124.5
101~187
118~218
134.5~249.5
Type
Model Name
Power Supply
Capacity Range
0.6ton
0.8ton
1ton
1.5ton
2ton
2.5ton
3ton
4ton
VJU
Capacity Index
7.5
9.5
12
18
24
30
36
48
Ceiling Mounted Cassette
Type (Multi Flow)
FXFQ
—
—
12M
18M
24M
30M
36M
—
Slim Ceiling Mounted
Duct Type
FXDQ
07M
09M
12M
18M
24M
—
—
—
Ceiling Mounted Built-In
Type
FXSQ
—
—
12M
18M
24M
30M
36M
48M
Ceiling Mounted Duct
Type
FXMQ
—
—
—
—
—
30M
36M
48M
Ceiling Suspended Type
FXHQ
—
—
12M
—
24M
—
36M
—
Wall Mounted Type
FXAQ
07M
09M
12M
18M
24M
—
—
—
Floor Standing Type
FXLQ
—
—
12M
18M
24M
—
—
—
Concealed Floor
Standing Type
FXNQ
—
—
12M
18M
24M
—
—
—
New refrigerant model code
07 type
09 type
12 type
18 type
24 type
30 type
36 type
48 type
Selecting model capacity
7,500
Btu/h
9,500
Btu/h
12,000
Btu/h
18,000
Btu/h
24,000
Btu/h
30,000
Btu/h
36,000
Btu/h
48,000
Btu/h
Equivalent output
0.6 ton
0.8 ton
1 ton
1.5 ton
2
ton
2.5 ton
3 ton
4 ton
Содержание BSVQ36MVJU
Страница 16: ...SiUS39 601 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 11 ...
Страница 115: ...Field Setting SiUS39 601 104 Test Operation ...
Страница 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Страница 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Страница 235: ...Wiring Diagrams for Reference SiUS39 601 224 Appendix 2 2 Field Wiring RXYQ72 96MTJU C 3D042647B ...
Страница 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Страница 239: ...Wiring Diagrams for Reference SiUS39 601 228 Appendix FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 240: ...SiUS39 601 Wiring Diagrams for Reference Appendix 229 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 249: ...Example of Connection SiUS39 601 238 Appendix ...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix ...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Страница 269: ...SiUS39 601 iv Index ...