SiUS39-601
Protection Control
Function
51
4.3
Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against a malfunction or transient increase of discharge pipe temperature.
★
Each compressor performs the discharge pipe temperature protection control individually in
the following sequence.
[INV compressor]
[STD compressor]
In discharge pipe temp.
protection control
HTdi>230˚F
Tp>239˚F
HTdi : Value of INV compressor discharge pipe
temperature (Tdi) compensated with
outdoor air temperature
Tp :
Value of compressor port temperature
calculated by Tc and Te, and suction
superheated degree.
or
Discharge pipe temp.
protection control not limited
Discharge pipe
temp.control standby
INV upper limit frequency:
1-step down from current
compressor frequency
INV upper limit frequency: 1-step up
from current compressor frequency
INV62 Hz + OFF
HTdi>230˚F
Tp>239˚F
or
Every 30 sec.
HTdi>275˚F
HTdi>239˚F for 10 min. or more.
or
HTdi<221˚F
Tp<239˚F
&
Every 60 sec.
HTdi>266˚F
HTdi>239˚F
for 90 sec.
or more.
Tp>266˚F
or
HTdi<203˚F
Tp<212˚F
&
When occurring 3 times within 100 minutes,
the malfunction code “F3” is output.
• HTds>239˚F continues for 5 min. or more.
• HTds>275˚F
• Tp>239˚F continues for 10 min. or more.
• Tp>266˚F
or
Applicable STD
compressor stops.
10 min.
Discharge pipe temp.
protection control not limited
HTds : Value of STD compressor discharge
pipe temperature (
Tds) compensated
with outdoor air temperature
Tp :
Value of compressor port temperature
calculated by Tc and Te , and suction
superheated degree.
Содержание BSVQ36MVJU
Страница 16: ...SiUS39 601 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 11 ...
Страница 115: ...Field Setting SiUS39 601 104 Test Operation ...
Страница 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Страница 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Страница 235: ...Wiring Diagrams for Reference SiUS39 601 224 Appendix 2 2 Field Wiring RXYQ72 96MTJU C 3D042647B ...
Страница 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Страница 239: ...Wiring Diagrams for Reference SiUS39 601 228 Appendix FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 240: ...SiUS39 601 Wiring Diagrams for Reference Appendix 229 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 249: ...Example of Connection SiUS39 601 238 Appendix ...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix ...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Страница 269: ...SiUS39 601 iv Index ...