Troubleshooting by Indication on the Remote Controller
SiUS39-601
136
Troubleshooting
2.14
“
E3
”
Outdoor Unit:
Actuation of High Pressure Switch
Remote
Controller
Display
E3
Applicable
Models
RXYQ72M, 96M
Method of
Malfunction
Detection
Abnormality is detected when the contact of the high pressure protection switch opens.
Malfunction
Decision
Conditions
Error is generated when the HPS activation count reaches the number specific to the operation
mode.
Supposed
Causes
Actuation of outdoor unit high pressure switch
Defect of High pressure switch
Defect of outdoor unit PC board
Instantaneous power failure
Faulty high pressure sensor
Troubleshooting
★
1: Actuation of high pressure switch (HPS)
• The outdoor unit PC board’s connector is disconnected.
• Is the outdoor unit heat exchanger dirty?
• Defect of outdoor fan
• Is the refrigerant over-charged?
• Faulty high pressure sensor
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Operation
is normal when turned
on again by remote
controller.
Replace outdoor unit PC board
(A1P).
Actuation of high pressure switch.
+
1
YES
YES
There was an instantaneous
power failure or a past safety
device actuated. Re-check
refrigerant system.
NO
NO
(V3065)
Contact
S1PH or S2PH
is open.
Connect the connector and
operate again.
NO
YES
Are the HPS
connectors connected
to the outdoor main
P.C.Board?
+
1
Содержание BSVQ36MVJU
Страница 16: ...SiUS39 601 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 11 ...
Страница 115: ...Field Setting SiUS39 601 104 Test Operation ...
Страница 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Страница 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Страница 235: ...Wiring Diagrams for Reference SiUS39 601 224 Appendix 2 2 Field Wiring RXYQ72 96MTJU C 3D042647B ...
Страница 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Страница 239: ...Wiring Diagrams for Reference SiUS39 601 228 Appendix FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 240: ...SiUS39 601 Wiring Diagrams for Reference Appendix 229 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 249: ...Example of Connection SiUS39 601 238 Appendix ...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix ...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Страница 269: ...SiUS39 601 iv Index ...