SiUS39-601
Troubleshooting (OP: Schedule Timer)
Troubleshooting
207
4.5
“
MC
”
Address Duplication, Improper Setting
Remote
Controller
Display
MC
Applicable
Models
schedule timer
Method of
Malfunction
Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Decision
Conditions
When two or more schedule timers are connected.
Supposed
Causes
Address duplication of schedule timer
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2840)
Are two or more
schedule timer
connected?
Reset the power supply for the
schedule timer.
Disconnect all schedule timer
except one and reset the
schedule timer’s power supply.
YES
NO
Содержание BSVQ36MVJU
Страница 16: ...SiUS39 601 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 11 ...
Страница 115: ...Field Setting SiUS39 601 104 Test Operation ...
Страница 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Страница 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Страница 235: ...Wiring Diagrams for Reference SiUS39 601 224 Appendix 2 2 Field Wiring RXYQ72 96MTJU C 3D042647B ...
Страница 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Страница 239: ...Wiring Diagrams for Reference SiUS39 601 228 Appendix FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 240: ...SiUS39 601 Wiring Diagrams for Reference Appendix 229 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 249: ...Example of Connection SiUS39 601 238 Appendix ...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix ...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Страница 269: ...SiUS39 601 iv Index ...