Specifications
SiUS39-601
20
Specifications
Wall Mounted Type
Notes:
★
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25ft (Horizontal)
★
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
★
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model
FXAQ18MVJU
FXAQ24MVJU
★
1 Cooling Capacity
Btu/h
18,000
24,000
★
2 Heating Capacity
Btu/h
20,000
27,000
Casing Color
White (3.0Y8.5/0.5)
White (3.0Y8.5/0.5)
Dimensions: (H×W×D)
in
11–3/8×41–3/8×9
11–3/8×41–3/8×9
Coil (Cross
Fin Coil)
Rows × Stages × FPI
2×14×17
2×14×17
Face Area
ft²
2.29
2.29
Fan
Model
QCL9686
QCL9686
Type
Cross Flow Fan
Cross Flow Fan
Motor Output
HP
0.058
0.058
Air Flow Rate (H/L)
cfm
500/400
635/470
Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat for Cooling and Heating
Microprocessor Thermostat for Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Air Filter
Resin Net (Washable)
Resin Net (Washable)
Piping
Connections
Liquid Pipes
in
φ
1/4 (Flare Connection)
φ
3/8 (Flare Connection)
Gas Pipes
in
φ
1/2 (Flare Connection)
φ
5/8 (Flare Connection)
Drain Pipe
in
VP13
(External Dia. 11/16 Internal Dia. 1/2)
VP13
(External Dia. 11/16 Internal Dia. 1/2)
Machine Weight (Mass)
Lbs
31
31
★
4 Sound Level (H)
dBA
43
47
Safety Devices
Fuse
Fuse
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Connectable outdoor unit
R-410A Series
R-410A Series
Standard Accessories
Operation Manual, Installation Manual, Installation Panel,
Paper Pattern for Installation, Insulation Tube, Clamps,
Screws.
Operation Manual, Installation Manual, Installation Panel,
Paper Pattern for Installation, Insulation Tube, Clamps,
Screws.
Drawing No.
C:3D046038A
Содержание BSVQ36MVJU
Страница 16: ...SiUS39 601 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 11 ...
Страница 115: ...Field Setting SiUS39 601 104 Test Operation ...
Страница 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Страница 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Страница 235: ...Wiring Diagrams for Reference SiUS39 601 224 Appendix 2 2 Field Wiring RXYQ72 96MTJU C 3D042647B ...
Страница 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Страница 239: ...Wiring Diagrams for Reference SiUS39 601 228 Appendix FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 240: ...SiUS39 601 Wiring Diagrams for Reference Appendix 229 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 249: ...Example of Connection SiUS39 601 238 Appendix ...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix ...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Страница 269: ...SiUS39 601 iv Index ...