Specifications
SiUS39-601
12
Specifications
Ceiling Mounted Cassette Type (Multi-flow)
Notes:
★
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length : 25ft (Horizontal)
★
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
★
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model
FXFQ30MVJU
FXFQ36MVJU
★
1 Cooling Capacity
Btu/h
30,000
36,000
★
2 Heating Capacity
Btu/h
34,000
40,000
Casing / Color
Galvanized Steel Plate
Galvanized Steel Plate
Dimensions: (H×W×D)
in
11-3/8
×
33-1/8
×
33-1/8
11-3/8
×
33-1/8
×
33-1/8
Coil (Cross
Fin Coil)
Rows × Stages × FPI
2
×
12
×
17
2×12×17
Face Area
ft²
5.35
5.35
Fan
Model
QTS45A17M
QTS45A17M
Type
Turbo Fan
Turbo Fan
Motor Output
HP
0.12
0.12
Air Flow Rate (H/L)
cfm
990/710
990/740
Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat for Cooling and Heating
Microprocessor Thermostat for Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Piping
Connections
Liquid Pipes
in
φ
3/8 (Flare Connection)
φ
3/8 (Flare Connection)
Gas Pipes
in
φ
5/8 (Flare Connection)
φ
5/8 (Flare Connection)
Drain Pipe
in
VP25
External Dia. 1-1/4
Internal Dia. 1
VP25
External Dia. 1-1/4
Internal Dia. 1
Machine Weight (Mass)
Lbs
66
66
★
4 Sound Level (H/L)
dBA
38/32
40/33
Safety Devices
Fuse, Thermal Protector for Fan Motor
Fuse, Thermal Protector for Fan Motor
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Connectable outdoor unit
R-410A Series
R-410A Series
Decoration
Panels
(Option)
Model
BYC125K-W1
BYC125K-W1
Color
White (10Y9/0.5)
White (10Y9/0.5)
Dimensions: (H×W×D)
in
1-5/8
×
37-3/8
×
37-3/8
1-5/8
×
37-3/8
×
37-3/8
Air Filter
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Weight
Lbs
11
11
Standard Accessories
Operation manual, Installation manual, Paper pattern for
installation, Drain hose, Clamp metal, Washers, Sealing
pads, Clamps, Screws, Insulation for fitting.
Operation manual, Installation manual, Paper pattern for
installation, Drain hose, Clamp metal, Washers, Sealing
pads, Clamps, Screws, Insulation for fitting.
Drawing No.
C:3D042686
(
)
(
)
Содержание BSVQ36MVJU
Страница 16: ...SiUS39 601 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 11 ...
Страница 115: ...Field Setting SiUS39 601 104 Test Operation ...
Страница 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Страница 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Страница 235: ...Wiring Diagrams for Reference SiUS39 601 224 Appendix 2 2 Field Wiring RXYQ72 96MTJU C 3D042647B ...
Страница 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Страница 239: ...Wiring Diagrams for Reference SiUS39 601 228 Appendix FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 240: ...SiUS39 601 Wiring Diagrams for Reference Appendix 229 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 249: ...Example of Connection SiUS39 601 238 Appendix ...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix ...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Страница 269: ...SiUS39 601 iv Index ...