SiUS39-601
Protection Control
Function
53
4.5
STD Compressor Overload Protection
This control is used to prevent abnormal heating due to overcurrent to the compressor resulting
from failures of STD compressor such as locking.
STD compressor ON
CT detection current value>A
for more than 3 sec.
STD compressor OFF for 30 min.
Demand to operate.
A
28.8A
When occurring 3 times within 90 minutes,
the malfunction code “ E6 ” is output.
current > 30A
MgS Reset
OC function
→
MgS off
Содержание BSVQ36MVJU
Страница 16: ...SiUS39 601 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 11 ...
Страница 115: ...Field Setting SiUS39 601 104 Test Operation ...
Страница 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Страница 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Страница 235: ...Wiring Diagrams for Reference SiUS39 601 224 Appendix 2 2 Field Wiring RXYQ72 96MTJU C 3D042647B ...
Страница 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Страница 239: ...Wiring Diagrams for Reference SiUS39 601 228 Appendix FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 240: ...SiUS39 601 Wiring Diagrams for Reference Appendix 229 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 249: ...Example of Connection SiUS39 601 238 Appendix ...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix ...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Страница 269: ...SiUS39 601 iv Index ...