Field Setting
Test Operation
87
8
: ON
7
: OFF
9
: Blink
Setting item 0 Display contents of “Number of units for sequential start, and
others”
No.
Setting item
LED display
Data display
H1P
H2P
H3P
H4P
H5P
H6P
H7P
0
Number of units for sequential
starting, and others
9 7 7 7 7 7 7
See below
1
C/H unified address
9 7 7 7 7 7 8
Lower 6 digits
2
Low noise/demand address
9 7 7 7 7 8 7
3
Not used
9 7 7 7 7 8 8
4
Airnet address
9 7 7 7 8 7 7
5
Number of connected indoor units
9 7 7 7 8 7 8
6
Number of connected BS units
9 7 7 7 8 8 7
7
Number of connected zone units
(excluding outdoor and BS unit)
9 7 7 7 8 8 8
8
Number of outdoor units
9 7 7 8 7 7 7
9
Number of connected BS units
9 7 7 8 7 7 8
Lower 4 digits:
upper
10
Number of connected BS units
9 7 7 8 7 8 7
Lower 4 digits:
lower
11
Number of zone units (excluding
outdoor and BS unit)
9 7 7 8 7 8 8
Lower 6 digits
12
Number of terminal blocks
9 7 7 8 8 7 7
Lower 4 digits:
upper
13
Number of terminal blocks
9 7 7 8 8 7 8
Lower 4 digits:
lower
14
Contents of malfunction (the latest)
8 7 7 8 8 8 7
Malfunction
code table
Refer page
118,119.
15
Contents of malfunction
(1 cycle before)
8 7 7 8 8 8 8
16
Contents of malfunction
(2 cycle before)
8 7 8 7 7 7 7
20
Contents of retry (the latest)
8 7 8 7 8 7 7
21
Contents of retry (1 cycle before)
8 7 8 7 8 7 8
22
Contents of retry (2 cycle before)
8 7 8 7 8 8 7
Number of units for sequential
start
1 unit
9 7 7 7 7 7 7
2 units
9 7 9 7 7 7 7
3 units
9 7 8 7 7 7 7
EMG operation /backup operation
setting
ON
9 7 7 8 7 7 7
OFF
9 7 7 7 7 7 7
Defrost select setting
Short
9 7 7 7 8 7 7
Medium
9 7 7 7 9 7 7
Long
9 7 7 7 7 7 7
Te setting
H
9 7 7 7 7 8 7
M
9 7 7 7 7 9 7
L
9 7 7 7 7 7 7
Tc setting
H
9 7 7 7 7 7 8
M
9 7 7 7 7 7 9
L
9 7 7 7 7 7 7
c. Monitor mode
<Selection of setting item>
<Confirmation on setting contents>
To enter the monitor mode, push the
MODE button (BS1) when in
“Setting mode 1”.
Push the SET button (BS2) and set
the LED display to a setting item.
Push the RETURN button (BS3) to
display different data of set items.
Push the RETURN button (BS3) and
switches to the initial status of
“Monitor mode”.
∗
Push the MODE button (BS1) and
returns to “Setting mode 1”.
(V2765)
Содержание BSVQ36MVJU
Страница 16: ...SiUS39 601 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 11 ...
Страница 115: ...Field Setting SiUS39 601 104 Test Operation ...
Страница 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Страница 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Страница 235: ...Wiring Diagrams for Reference SiUS39 601 224 Appendix 2 2 Field Wiring RXYQ72 96MTJU C 3D042647B ...
Страница 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Страница 239: ...Wiring Diagrams for Reference SiUS39 601 228 Appendix FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 240: ...SiUS39 601 Wiring Diagrams for Reference Appendix 229 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 249: ...Example of Connection SiUS39 601 238 Appendix ...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix ...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Страница 269: ...SiUS39 601 iv Index ...