SiUS39-601
Troubleshooting by Indication on the Remote Controller
Troubleshooting
171
2.40
“
PJ
”
Outdoor Unit:
Faulty Field Setting after Replacing
Main PC Board or Faulty Combination of PC Board
Remote
Controller
Display
PJ
Applicable
Models
RXYQ72M, 96M
Method of
Malfunction
Detection
The faulty (or no) field setting after replacing main PC board or faulty PC board combination is
detected through communications with the inverter.
Malfunction
Decision
Conditions
Whether or not the field setting or the type of the PC board is correct through the communication
date is judged.
Supposed
Causes
Faulty (or no) field setting after replacing main PC board
Mismatching of type of PC board
Troubleshooting
YES
Reset, and then restart.
YES
YES
∗
Note) Type of PC board mismatching includes;
Main PC board
Inverter PC board (for compressor)
Fan driver PC board
NO
NO
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Correct the field
settings.
Replace with a correct
PC board.
Has the PC
board been replaced?
Is the type of
PC board correct?
∗
When replacing
the main PC board, were field
setting properly
made?
Содержание BSVQ36MVJU
Страница 16: ...SiUS39 601 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 11 ...
Страница 115: ...Field Setting SiUS39 601 104 Test Operation ...
Страница 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting ...
Страница 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M ...
Страница 235: ...Wiring Diagrams for Reference SiUS39 601 224 Appendix 2 2 Field Wiring RXYQ72 96MTJU C 3D042647B ...
Страница 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A ...
Страница 239: ...Wiring Diagrams for Reference SiUS39 601 228 Appendix FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 240: ...SiUS39 601 Wiring Diagrams for Reference Appendix 229 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 249: ...Example of Connection SiUS39 601 238 Appendix ...
Страница 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix ...
Страница 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A ...
Страница 269: ...SiUS39 601 iv Index ...