M8610-FAN
<60W
M8606-FAN
<60W
M8606-FAN B
<150W
Consumption of power supplies
Power Modules
Maximum Output Power (W)
RG-PA1200
1200 W
RG-PA2000
90
–176 VAC, power: 1200 W;
176
–264 VAC, power: 2000 W
RG-PA1200E
1200 W
RG-PA1200I
90
–176 VAC, power:530 W;
176
–264 VAC, power:1400 W
RG-PA2000I
90
–176 VAC, power:1080 W;
176
–264 VAC, power:2000 W
RG-PA800IF(It can be used in the S8606 B chassis only.)
90
–176 VAC, power: 400 W;
176
–264 VAC, power: 800 W
RG-PD1200
1200 W
RG-PD2000
2000 W
The following example shows how to select the power supplies according to the used modules.
For example, a user purchases one S8608 chassis, two M8600-24GT/12SFP-EC line cards, two M8606-CM II line cards
and two M8600-02XFP24SFP/12GT-EC line cards. The total power consumption of these modules is 514W
(M8606-FAN+2xM8600-24GT/12SFP-EC+2xM8606-CM
II+2xM8600-02XFP24SFP/12GT-EC=60+77x2+50x2+100x2=514), which is larger than 1200W. One RG-PA1200 power
module with the maximum output power being 1200W can be used to guarantee the normal system operation. The user
can also purchase two RG-PA1200 power modules for the 1+1 power supply redundancy.
Cabinet Installation
Precautions
When you install the cabinet, pay attention to the following:
All expansion screws for fastening the cabinet base to the ground should be installed and tightened in sequence
from bottom to up (large plain washer, spring washer, and nut), and the installation holes on the base and the
expansion screws should be well aligned.
After the cabinet is installed, it should be stable and still.
After the cabinet is installed, it should be vertical to the ground.
When multiple cabinets are put side by side in the room, they should be aligned in a straight line, with an error less
than 5 mm.
The front/back doors of the cabinet should be properly installed. You can open and close them smoothly. The locks
should work normally, and the keys should be complete.
There should be no unnecessary or informal labels inside the cabinet and on various boards.
Blank panels should be installed completely.
Fastening screws of various devices in the cabinet of the same model should be complete and tightened.
Various boards of the equipment should be installed securely, and the fastening screws on the panel should be
tightened.
All wiring outlets at the top and bottom of the cabinet should be installed with rodent-resistant nets where the seams
should be no more than 1.5 cm in diameter, to prevent rodents and other small animals from entering the cabinet.
Antistatic wrist straps should be provided in the cabinet.
Simple Installation Steps
1)
Plan the available space before installing the cabinet. You must reserve sufficient space for front and back doors for
maintenance.
2)
Mount and fasten the 19-inch cabinet at the specified location.
3)
Install the appropriate chute and cables.
Содержание RG-S8606 B
Страница 1: ...RG S8600 Series Switch Hardware Installation and Reference Guide V1 78 ...
Страница 58: ...Figure 2 3 Moving the RG S8606 Switch Figure 2 4 Moving the RG S8606 B Switch ...
Страница 62: ...Figure 2 6 Ventilation of RG S8614 ...
Страница 63: ...Figure 2 7 Ventilation of RG S8610 Figure 2 8 Ventilation of RG S8606 ...
Страница 76: ...Figure 3 8 Installing the Power Supply of the RG S8606 Switch ...
Страница 92: ...Figure 3 34 Board Components of the RG S8610 Figure 3 35 Board Components of RG S8606 ...