telephone number, account info etc. in order to report to the central station properly. Refer to the
5104B manual for further information. Once the wiring and programming of the CP-3500D and 5104B
are complete, any alarms, supervisory or trouble conditions with either the CP-3500D or the 5104B
will be communicated off premises to a central station receiver.
Figure 8
7.1.4 Operation
When an alarm is received by the CP-3500D, one of the alarm relays A, B, C or D will trip and
activate the appropriate zone on the 5104B communicator. The 5104B will transmit the notification to
the central station. Acknowledging the alarm on the CP-3500D will only silence its internal sounder.
The sounder on the 5104B CANNOT be silenced by pressing the ALARM ACK key on the CP-3500D
or the Reset/Silence switch on the communicator. The 5104B will silence its sounder and fully reset
only when the CP-3500D RESET key is pressed and the 5104B has finished communicating to the
central station.
When a supervisory alarm is received by the CP-3500D, the Alarm C relay will short causing a
supervisory transmission to be sent from Zone 4 on the 5104B. Acknowledging the supervisory on the
CP-3500D will only silence its internal sounder. Pressing the Reset/Silence switch on the 5401B will
silence its internal sounder. The 5104B will also silence its sounder and fully reset when the CP-
3500D is reset either when the RESET key is pressed or all self-restoring supervisory are restored.