sure the affected unit has power and perform a signal survey test or power cycle the unit. If the
problem persists the unit will require factory service.
10.
Charger Fault
– Can occur in an WRA-3, SR-5, AR-5 repeater or CP-3500D panel. Caused by
problem in battery charging circuit. Unit will require factory service.
11.
Low Battery
– Can occur in any CWSI battery operated or A/C powered device, repeater or
CP-3500D panel. Caused by battery voltage being too low or faulty batteries. Let the batteries
charge or replace the batteries.
12.
Maintenance Req
– Can occur in models 300, 301, 302, 325 detectors. Caused by dirt in the
smoke chamber or hardware failure in the smoke detector head. Clean the smoke detector. If
the problem persists, replace the unit.
13.
Power Up Reset
– Will occur when any enrolled device is powered up. This is a normal
occurrence and does not indicate a trouble. A trouble is indicated If the device sends a Power
Up Reset signal any time after initial power up. If this occurs, the unit should be returned to the
factory for repair.
14.
Unknown Unit
–
Can occur when a device, annunciator or repeater that is not enrolled is
checking into the CP-3500D control panel. Refer to section 4.9 in this manual for more
information.
15.
Memory Error
–
Will occur if the CP-3500D is unable to access any of its internal memory.
The display will show “Unable to access memory device”. This trouble requires factory service.
16.
Dialer Fault
–
Will occur when the Keltron dialer option has been programmed as active and
the CP-3500D trouble input detects an open circuit or there is a communication problem
between TB5 and the serial port on the Keltron SDACT(-2). This trouble condition is self-
restoring.
17.
Checksum Bad
–
Will occur when the programming information between the CP-3000A and
any enrolled annunciator does not match. Program the annunciator(s) as described in the
WRA-3 manual.
Self-Restoring Trouble List
MODEL #
TROUBLE CONDITION
CP-3500D
AC POWER LOSS, GROUND FAULT,DIALER FAULT
AR-5
AC POWER LOSS, GROUND FAULT, TEST FAILURE
SR-5
AC POWER LOSS, TEST FAILURE , TROUBLE( IN 24
VOLT MODE)
WRA-3
AC POWER LOSS, TEST FAILURE
301,302
TAMPER, MAINT REQUIRED,HARDWARE
FAULT,TEST FAILURE
310
TAMPER,TEST FAILURE
320
TAMPER,TEST FAILURE
325
TAMPER TEST FAILURE
345(TS)
TAMPER ,EOL,TEST FAILURE TROUBLE( WHEN
CONFIGURED AS REMOTE TROUBLE)
350
TAMPER, MAINT REQUIRED,TEST FAILURE
Table 3
Содержание CP-3500D
Страница 12: ...P N IM C35KD Rev C 2014 Commercial Wireless Systems International LLC 12 Figure 1...
Страница 21: ...P N IM C35KD Rev C 2014 Commercial Wireless Systems International LLC 21 Figure 2...
Страница 47: ...P N IM C35KD Rev C 2014 Commercial Wireless Systems International LLC 47 Figure 4...