P/N IM-C35KD Rev. C
2014 Commercial Wireless Systems International, LLC.
40
4.6.2 CP-3500D Relay Programming
The screen is divided into two sections, turn on and turn off. These outputs can only be activated with
an alarm signal. You can choose any
one
of the alarm priorities A, B, C, or D to activate each output.
The alarm priorities are explained in section 4.4.4 of this manual. An X in any of the turn on fields
means that output is not programmed to activate. An output will be activated when an alarm signal is
received from a device whose priority matches the programming selection for that output. Once an
output is activated, it can only be deactivated or turned off manually by pressing a button. Pressing
the RESET button will always deactivate the outputs. In addition to the RESET button, the SIGNAL
SILENCE button can also be programmed to deactivate an output. The default to turn off these
outputs is Signal Silence. The available selections are Signal Silence and Reset. Selecting Reset will
keep the output activated until the RESET button is pressed.
To change a turn on field, move the cursor to the desired turn on output field and press ENTER. Use
the UP/DOWN buttons to select the alarm priority then press ENTER to exit edit mode. Press the
save soft key to save your changes or the cancel soft key to abort the changes.
Important: Any device programmed for sprinkler supervisory as detailed in sections 4.4.4 and
4.7 of this manual will NOT activate the relay 1, relay 2 or Auxiliary outputs even if
programmed to do so.
To change a turn off field, move the cursor to the desired turn off button output field and press
ENTER. Use the UP/DOWN buttons to change the selection to Reset then press ENTER to exit edit
mode. Press the save soft key to save your changes or cancel to abort the changes.
4.7 Supervisory Setup
The CP-3500D can be used for supervisory applications. The CP-3500D can be programmed to
display sprinkler supervisory alarms from devices programmed for alarm priority C. One application
example would be a model 345(TS) Fire Transmitter whose input is wired to monitor a water flow
tamper switch. Only alarm priority C can be used for this application.
Important: All of the following
items MUST be adhered to for a sprinkler supervisory alarm to report properly.
1. Any model 345(TS) Fire Transmitter used for sprinkler supervisory must be
programmed for alarm priority C.
2. The sprinkler supervisory feature of the CP-3500D must be turned on as described in
this section.
3. Select the appropriate device type for the sprinkler supervisory transmitters as
required for the application.
The supervisory signals can also be programmed to auto-restore. This option if desired should be
chosen during system setup if possible. Turning supervisory auto-restore or alarm C supervisory on
or off after devices are programmed to alarm level C will require a system reboot.
4.7.1 Accessing the Supervisory Setup Screen
To access the CP-3500D supervisory setup screen, press the program soft key on the main system
normal screen. Scroll down to CP-3500D Setup and press ENTER. The CP-3500D setup menu will
now be displayed. Highlight Supervisory Setup and press ENTER. The following screen will be
displayed.