The second option is the function of the third zone position on a model 301. The first two zones work
the same as any other device however the third zone on a model 301 is unique. Two or more model
301 tandems with the same zone number in the third zone entry position
will not
activate each
other’s sounders when they are in alarm. This only applies to a model 301. An alarm from any other
device such as a model 345(TS) with any zone position matching the model 301 third zone
will
activate that detectors sounder.
The Model 301 tandem smoke detectors can also be manually activated and deactivated using
buttons on the keypad. Manual activation and deactivation of tandem sounders is a global function
and will affect ALL Model 301 tandem smoke detectors in the installation. The Horns On button can
be programmed to manually activate the tandem detector sounders. The Detector sounder silence or
Reset button can be programmed to deactivate the tandem detector sounders. These buttons must
be programmed in the CP-3500D to provide these functions.
Note: Silencing a tandem smoke
detector sounder may take up to 60 seconds.
4.8.1 Two Alarm Zone operation
The zones 800-899 require two devices on the same zone to be in alarm for the zone to become
activated and turn on NAC’s, relays, tandems etc. When the first device with the zone goes into alarm
it will show on the CP-3500D as an alarm condition but any programmed functions using that zone
will not activate unless and until a second device also goes into alarm.
4.8.2 Accessing the Tandem Control Menu
Manual activation and deactivation of the tandem smoke detectors can be programmed under the AV
Device/Tandem Controls program menu item. To access this menu press the program soft key on the
main system normal screen. Scroll down to AV Device/Tandem Controls and press ENTER. The
setup menu will now be displayed as shown below.
4.8.3 Programming Tandem Manual Activation and Deactivation
Move the cursor to the Device Type field and press enter. Use the down button and change the field
to the Tandem Smoke Det. Selection and press enter. The A/V Device and Tandem CO Det choices
are for future use. Press the save soft key to go back to the main screen to program the on and off
A V D e v ic e / T a n d e m D e t e c t o r s
Ca n c e l
S e l e c t b u t t o n t o m a n u a l l y c o n t r o l a l l
A V D e v i c e / T a n d e m D e t e c t o r S o u n d e r s
D e v i c e T y p e : A / V D e v i c e
D e v i c e O n : H o r n s O n
D e v i c e O f f : R e s e t