The trouble title will be shown at the top of the screen along with the time and date. The page up and
page down soft keys will appear when number of signals spans more than one LCD page. Use these
keys to view trouble signals on other pages.
Below is a list of trouble signals with causes and possible solutions.
1.
Power Loss
– Can occur in models WRA-3, SR-5, AR-5 or CP-3500D control panel. Caused
by low or no voltage present at A/C input to product. CP-3500D trouble relay activation will be
delayed by 120 minutes. Check the A/C power source for the affected unit. This trouble is self-
restoring.
2.
Ground Fault
– Can occur in an AR-5 repeater or CP-3500D control panel. Caused by a NAC
or Auxiliary output wiring short to earth ground of 1000 ohms or less. Check the wiring for
shorts to earth ground. This trouble is self-restoring.
3.
Hardware Fault
– Can occur in a CP-3500D panel or model 301 smoke detector. Caused by
loss of communications between the receiver and main CP-3500D board or a smoke detector
internal component problem. Power cycle the CP-3500D or smoke detector. If the problem
persists, the unit needs factory service.
4.
Aux Circuit
– Can occur in a CP-3500D control panel. Caused by an open in the wiring
connected to the Aux circuit. Check the wiring for opens.
5.
Tamper
– Can occur in any battery operated device. Caused by removal of device or exposing
device battery. Make sure the device is mounted correctly.
6.
Tamper/Maint
– Can occur in a model 350 CO detector. Caused by removal of the device,
open sensor or sensor end of life.
7.
Test Failure
– Can occur in an AR-5 repeater or any device. Caused by the CP-3500D not
receiving a device polling transmission within 200 seconds. Check to see if the affected unit
has power. Perform a signal survey from the device and verify it is good.
8.
EOL Violation
– Can occur in an AR-5 repeater or CP-3500D panel. Caused by an open
circuit or short circuit in the NAC wiring preventing the unit from reading the end of line resistor.
Check the wiring for shorts and opens.
9.
Program Fail
– Can occur in an AR-5 repeater or CP-3500D control panel. Caused when an
AR-5 repeater or CP-3500D control panel does not accept programming commands. Make
1 2 : 0 0 : 0 0 P M T r o u b l e 0 1 / 0 1 / 0 9
P a g e U p P g D o w n
T a m p e r 0 1 8 a 5 d 1 1 : 5 9 : 0 0 P M 0 1 / 0 1 / 0 9
S m o k e D e t S o u t h H a l l w a y
L o w B a t t e r y 0 2 3 a 6 2 1 2 : 0 1 : 0 4 A M 0 1 / 0 2 / 0 9
P u l l S t a t i o n S t a i r w e l l B
E O L V i o l a t i o n 0 4 8 1 1 d 1 2 : 0 5 : 0 0 A M 0 1 / 0 2 / 0 9
C P - 3 0 0 0 D
Trouble title
showing
Use page up
and down soft
keys to view
additional pages
In process
Trouble
signals
Содержание CP-3500D
Страница 12: ...P N IM C35KD Rev C 2014 Commercial Wireless Systems International LLC 12 Figure 1...
Страница 21: ...P N IM C35KD Rev C 2014 Commercial Wireless Systems International LLC 21 Figure 2...
Страница 47: ...P N IM C35KD Rev C 2014 Commercial Wireless Systems International LLC 47 Figure 4...