CTC GSi 16
Settings
Heating circuit 1
Heating circuit 2
Heat pump
Electric heater
DHW-tank
Communication
Cooling
Solar panels
Diff thermostat function
Pool
External heat source
EcoVent
Save settings
Load settings
Load factory settings
Heating circuit
Max primary flow ºC
60
Min primary flow ºC
Off
Heating, mode
Auto
Heating, mode, ext
Heating off, out ºC
18
Heating off, time
120
Inclination ºC
50
Adjustment ºC
0
Night reduction disable ºC
-14
Room temp reduced ºC
-2
or
Primary flow reduced ºC
-3
Alarm room temp ºC
5
Smart low price ºC
1
Smart over capacity ºC
2
Max time heating
20
Charge pump %
60
Drying period mode
Off
Drying period temp ºC
25
12.5.2 Settings
This menu is used to set the parameters for your
home’s heating requirements. It is important that this
basic setting is right for your home. Values which are
set incorrectly may mean that your property is not warm
enough or that an unnecessarily large amount of energy
is being used to heat your property.
Save settings
Here you can save your own settings.
Load settings
The saved settings can be reloaded using this option.
Load factory settings
The product is supplied with the factory values set.
They can be restored by activating this function. The
language, product and product size are retained.
Heating circuit 1 (or 2)
Max primary flow
60 (30—80)
The maximum permitted temperature to the radiators.
This functions as an electronic limiter to protect the floor
coils in underfloor heating systems.
Heating circuit 2 can only give the same temperature as
heating circuit 1 or a lower temperature.
Min primary flow
Off (Off,15—65)
You can use this option to set the minimum permitted
temperature if you want a specific level of background
heating during the summer in the basement or
underfloor heating coils, e.g. in the bathroom. The
heating in other parts of your property should then
be switched off using thermostatic radiator valves or
shut-off valves. Note that the radiator pump G2 will then
operate for the whole summer. This means that the
temperature supplied to the radiators will not fall below
a selected temperature, for e27°C.
Off means that the function is turned off.
i
Tip: Read more about these settings
in the section “Your home’s heating
settings”.
i
There is no radiator pump
in heating circuit 1. Instead,
“Heating, mode” is controlled by
the diverting valve.
Содержание GSi 16
Страница 6: ...6 CTC GSi 16...
Страница 48: ...48 CTC GSi 16 8 13 Tank schematic diagram A2...
Страница 49: ...49 CTC GSi 16...
Страница 50: ...50 CTC GSi 16 8 14 HP cooling module schematic diagram A5...
Страница 51: ...51 CTC GSi 16...
Страница 52: ...52 CTC GSi 16 8 15 Expansion card accessory schematic diagram A3 a CTC EcoZenith i350 CTC EcoVent i350F...
Страница 53: ...53 CTC GSi 16...
Страница 54: ...54 CTC GSi 16 M GF B25 B26 Y21 B5 G20 B24 B23 B27 B28 G11 G5 B102 B18...
Страница 61: ...61 CTC GSi 16...
Страница 119: ......
Страница 120: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 012 162 205 94 1 06 02 2019...